15
No.
Material
Model/Specifications
Quantity
1
Busbar A/B/C
N/A
1 PCS
2
Fuse
Rated voltage ≥ 500 V; rated current: 6 A
3 PCS
3
3P3E switch
The switch has a rated insulation voltage of 600 V, a rated
current of 15 A, and three poles. Kawamura NX53E-15W switch
is recommended.
1 PCS
8
Connecting a Cable to the DI Port
1. The SmartLogger provides eight DI ports, namely, DI1(GND1) to DI4(GND1) and DI5(GND2) to DI8(GND2).
An OVGR can connect to any DI port.
2. Two-core or multiple-core cables with a cross sectional area of 1.5 mm
2
are recommended.
No. Port
Function
1
GND1
Dry contact input common
terminal 1
2
DI1
DI_1
3
DI2
DI_2
4
DI3
DI_3
5
DI4
DI_4
6
DI5
DI_5
7
DI6
DI_6
8
DI7
DI_7
9
DI8
DI_8
10
GND2
Dry contact input common
terminal 2
2. Connect the AC1 and AC2 terminals at the other end of the cable to the
AC1
and
AC2
ports on
the SmartLogger respectively.
1. Connect one end of the delivered AC power cable to the 3P3E switch.