420010970304 - LP-700 Rev. 000 Rel. 002 Date 4.21.21
85
Table 32 - Boiler Error Codes
Important
Contact a qualified service technician for assistance if a Lockout Error occurs frequently. For safety reasons, the boiler will permit a maximum
of five (5) resets in 15 minutes (five [5] presses of the RESET button). A sixth (6th) attempt within this 15 minute period will lock out the boiler
permanently. The boiler will only operate again after the electrical supply has been disconnected and reconnected.
Repeated Lockout Error conditions could indicate a serious error with the boiler or installation. Failure to contact a qualified service technician
to troubleshoot the error could result in substantial property damage, serious personal injury, or death.
*Error is resettable remotely via HTP Tele-Diagnostic Service, HTP Remote Contractor.
Air Intake / Exhaust Gas Outlet
6 02
Exhaust NTC detects Vent Temperature is grea-
ter than 204°F (96°C)
Press the Reset button to clear the error code.
If Error happens again:
1. Check exhaust temperature sensor. Ensure connections are secure.
2. Check sensor resistance. If resistance is zero, replace the sensor.
3. Check flue gas temperature. Compare it to the reading on parameter 834. If the
parameter 834 reading is significantly higher, replace the flue sensor.
4. Check exhaust vent for blockage.
5. If the problem persists, check the combustion chamber and clean, if necessary.
Also, descale the heat exchanger.
6. If the problem persists, replace the control.
7. If the problem persists, replace the heat exchanger.
Blocking
(Manual
Reset)
6 03
APS Open
Press the Reset button to clear the error code.
1. Check APS and main controller connections. Ensure all are secure.
2. Check APS resistance. If resistance is not zero, replace the switch.
3. Check APS hose. Ensure it is connected and in good condition.
4. Check condensate line and termination for blockages.
5. Check exhaust vent for blockages.
6. If the problem persists, replace the main control.
6 05
Exhaust NTC circuit open or short circuit
This Error Code will go away when the condition is remedied.
1. Check exhaust temperature sensor. Ensure connections are dry and secure.
2. If flue is very cold, < 14°F (-10°C), remove sensor and warm it, then reinstall.
3. If flue is very hot – see error 6 02.
4. Check exhaust vent for blockages.
Blocking
(Auto
Reset)
6 12*
Insufficient fan speed
(<500 for 3 seconds or RPM min -300 for 3
minutes)
Press the Reset button to clear the error code.
If Error happens again:
1. Check the connections to the fan. Ensure all are secure.
2. If the fan does not rotate during the ignition sequence, check for 8Vac 26.5VDC
power at the fan connection.
If 8Vac 26.5VDC power is present at the control, replace the fan. If the blower
does not have 8Vac 26.5VDC power, check power at the control. If 8Vac 26.5VDC
power is not present at the control, replace the control.
3. If the problem persists, replace the main control.
Blocking
(Manual
Reset)
NOAVL PCB Error
1. Check parameter 046. If it is set to UNDEF, it must be changed according to the
boiler’s application. For example:
• b--SIN - Sets the boiler as a single boiler (default setting).
• b--MAS - Sets the master boiler of a cascade system.
• b--FL1 - Sets follower #1 of a cascade system.
• b--FL2 - Sets follower #2 of a cascade system.
• b--FL3 - Sets follower #3 of a cascade system.
• b--FL4 - Sets follower #4 of a cascade system.
• b--FL5 - Sets follower #5 of a cascade system.
• b--FL6 - Sets follower #6 of a cascade system.
• b--FL7 - Sets follower #7 of a cascade system.
2. If the problem persists, check the eBus2 wires. Ensure they are not shorted
together.
3. If the problem persists, replace the main control.
Display
Description
Possible Remedies
Error Type