
420010970304 - LP-700 Rev. 000 Rel. 002 Date 4.21.21
68
M
enu
Sub
-M
enu
Par
amet
er
Description
Value
Default Setting
2
5
8 Antilegionella frequency
24 - 720 (Hours), or 30 days
30 days
ELU WBN = Activated when the
boiler is connected to a tank by
an NTC sensor.
(Parameter 228 = 1)
2
6 BOILER MANUAL SETTINGS
Only to test components
2
6
0 Manual mode activation
0 = OFF, 1 = ON
0
2
6
1 Boiler pump control
0 = OFF, 1 = ON
0
Set Parameter 260=1
2
6
2 Fan control
0 = OFF, 1 = ON
0
Set Parameter 260=1
2
6
3 3 way valve control
0 = DHW, 1 = Heating
0
Set Parameter 260=1
2
7 TEST & UTILITIES
2
7
0 Test Mode
TEST+ = Max Heating power
TEST+ = Max DHW power
TEST+ = Minimum power.
TEST Mode can also be
activated by pressing the
Reset button for 10 seconds.
Test Mode deactivates after 30
minutes or by pressing Reset.
2
7
1 Air-purge cycle
0 = OFF, 1 = ON
See First Ignition section.
2
7
4
Floor drying cycle
0 = OFF
1 = Functional Heating
2 = Curing Heating
3 = Functional Heating
+ Curing Heating
4 = Curing Heating
+ Functional Heating
5 = Manual
0
2
7
5
Floor dry Supply setpoint temperature
77 - 140°F
131
2
8 RESET FACTORY SETTINGS
2
8
0
Automatically resets all parameters to the
factory defaults.
WARNING: Always check PCB settings
if restoring factory default settings on
a replacement controller. Replacement
controllers have generic settings that may not
be specific to the boiler model.
Reset: OK = yes,
ESC
= no
To Reset all parameter settings,
press the OK button.
2 10 OTHERS PARAMETERS
2 10 0 CH On Differential Temperature
0 - 36°F
11
Determines how much the boiler
outlet temperature can drop
below target before turning the
boiler back on.
2 10 1 DHW Modulation Setpoint
68 - 179°F
179
Boiler target temperature during
a DHW demand. Not applicable
for Combi models.
2 10 2 DHW On Differential Temperature
0 - 36°F
0
Determines how much the
DHW storage tank temperature
can drop below target before
initiating a DHW demand. Only
applicable when 2.2.8 = 1.
2 10 3 Emergency Setpoint
68 - 179°F
113
Sets Follower boiler
operating temperature when
communication with the Master
is lost, or when the System
Sensor is disconnected. See
Cascade Instruction Manual.
2 10 4 CH/DHW Shifting Priority Timer
0 - 1440 minutes
45
Determines how long a CH or
DHW demand can last before
the priority is switched. First
priority is with DHW. A value of
0 keeps the priority with DHW
indefinitely.