Table 28 - Complete Parameters List
8
3 BOILER CURRENT TEMPERATURES - Read Only
8
3
0 CH Supply Setpoint (in °F)
8
3
1 CH Supply Temperature (in °F)
8
3
2 CH Return Temperature (in °F)
8
3
3 DHW Outlet Temperature (in °F)
Not applicable to these models
8
3
4 Exhaust Flue Temperature (in °F)
8
3
5 Outdoor Temperature (in °F)
Only with outdoor sensor
connected
8
4 DHW TANK TEMPERATURE (ONLY ACTIVE WITH CONNECTED NTC TANK SENSOR) - Read Only
8
4
0 Displays current tank temperature (in °F)
Only with NTC tank sensor
connected
8
5 SERVICE
8
5
0
Months to next maintenance
0 - 60 (months)
12
If enabled (8.5.1 = 1), a notification is made on the display (and via the Tele-diagnostic Service, if applicable), warning that it
is time for maintenance
8
5
1 Enable Maintenance Warning
0 = OFF, 1 = ON
0
8
5
2
Maintenance Warning Reset
Reset? OK= Yes
, Esc = No
Resets Maintenance Advice and clears the Warning.
8
5
4 SW Version - Display Interface
8
5
5 SW Version - Main Controller
8
6 ERROR HISTORY
8
6
0
10 last errors
ERROR 0 - ERROR 9
This parameter displays the last 10 boiler errors, indicating the error code, day, month and year of occurence.
When the parameter is accessed, the errors are listed from ERROR 0 to ERROR 9.
8
6
1 Error list reset - Clears Error History
Reset? OK = y
es, ESC = no
8
7 FREE PARAMETERS - Read Only
8
7
0 NOT USED
8
7
1 NOT USED
8
7
2 NOT USED
8
7
3 NOT USED
8
7
4 Boiler flow switch
0= OFF, 1= ON
8
7
6 Safety flame sensor
0= OFF, 1= ON
8
7
8 Boiler power level (%)
0 - 100
(0 = minimum power,
100 = maximum power)
8
7
9 Boiler Flame Signal Measured by the Control
The flame signal must exceed 18 to initially detect the presence of
flame. Flame loss is detected if the signal drops below 15.