Table 27 - Complete Parameters List
M
enu
Sub
-M
enu
Par
amet
er
Description
Value
Default Setting
8
3
1
CH Supply Temperature (in °F)
8
3
2
CH Return Temperature (in °F)
8
3
3
DHW Outlet Temperature (in °F)
Not applicable to Non-Combi
models
8
3
4
Exhaust Flue Temperature (in °F)
8
3
5
Outdoor Temperature (in °F)
Only with outdoor sensor
connected
8
4 DHW TANK TEMPERATURE (ONLY ACTIVE WITH CONNECTED NTC TANK SENSOR) - Read Only
8
4
0
Displays current tank temperature (in °F)
Only with NTC tank sensor
connected
8
5 SERVICE
8
5
0
Months to next maintenance
0 - 60 (months)
12
If enabled (8.5.1 = 1), a notification is made on the display (and via the Tele-diagnostic Service, if applicable), warning that it
is time for maintenance
8
5
1
Enable Maintenance Warning
0 = OFF, 1 = ON
0
8
5
2
Maintenance Warning Reset
Reset? OK= Yes
, Esc = No
Resets Maintenance Advice and clears the Warning.
8
5
4
SW Version - Display Interface
8
5
5
SW Version - Main Controller
8
6 ERROR HISTORY
8
6
0
10 last errors
ERROR 0 - ERROR 9
This parameter displays the last 10 boiler errors, indicating the error code, day, month and year of occurence.
When the parameter is accessed, the errors are listed from ERROR 0 to ERROR 9.
8
6
1
Error list reset - Clears Error History
Reset? OK = y
es, ESC = no
8
7 FREE PARAMETERS - Read Only
8
7
0
NOT USED
8
7
1
NOT USED
8
7
2
NOT USED
8
7
3
NOT USED
8
7
4
Boiler flow switch
0= OFF, 1= ON
8
7
6
Safety flame sensor
0= OFF, 1= ON
8
7
8
Boiler power level (%)
0 - 100
(0 = minimum power,
100 = maximum power)
8
7
9
Boiler Flame Signal Measured by the Control
The flame signal must exceed 18
to initially detect the presence of
flame. Flame loss is detected if
the signal drops below 15.