LP-719 Rev. 000 Rel. 000 Date 6.25.20
59
L. Technical Menu - Complete Menu
M
enu
Sub
-M
enu
Par
amet
er
Description
Value
Default Setting
ACCESS the Complete Menu
1.
Simultaneously press the
“+”
and
“-”
buttons for 5 seconds. T
he display shows
222.
2. Press the
“+”
button to select
234
, the service code.
3. Press the
OK
button.
The display shows the first “quick setting”
PCB.
4. Press the
“+”
button until
the display shows
MENU.
5. Press the
OK
button to access the complete
menu
.
0 NETWORK
0
4 USER INTERFACE
0
4
0
Heating zone to be set from the home screen 1 = 1 Zone, 2 = 2 Zones,
3 = 3 Zones
1
0
4
1
Backlight timing
1 - 10 minutes or 24 hours
10
0
4
6
Cascade Boiler Configuration
UNDEF = undefined, b-SIN = sin-
gle boiler, b-MAS = master boiler,
b-FL1 = follower #1 boiler, b-FL2
= Follower #2, b-FL3 = Follower
#3, b-FL4 = Follower #4, b-FL5 =
Follower #5, b-FL6 = Follower #6,
b-FL7 = Follower #7
b--SIN
Reserved for Cascade applica-
tions. See Cascade Instruction
Manual for details.
0
4
7
Units
0 = Metric (
o
C), 1 = US (
o
F)
1
2 BOILER PARAMETERS
2
0 GENERAL
2
0
0
DHW Setpoint Temperature
WCN Models
97 - 140°F (36 to 60°C)
125
Also settable via the home
screen - see item
2
Figure 57
(not applicable when 2.2.8 = 2)
DHW Setpoint Temperature
WBN Models
104 - 149°F (40 to 65°C)
125
2
0
1
DHW Preheating
0 = Disabled, 1 = Enabled
1
Enables/disables comfort on/
off setting via COMFORT button
and parameter 2.5.0.
2
1 FREE PARAMETERS (DO NOT USE)
2
1
1
DO NOT USE
2
1
2
DO NOT USE
2
1
3
DO NOT USE
2
1
5
DO NOT USE
2
1
6
DO NOT USE
2
1
9
DHW Flow Detection Device Type
0 = Flow Switch, 1 = Flow Meter
1
Combi models use a flow meter.
Not applicable for non-Combi
models.
2
2 BOILER GENERAL SETTINGS
2
2
0
Ignition Power %
0 - 100
Must be set in accordance with Table 29.
2
2
3
Floor or Zone 2 Thermostat
0 = Floor safety thermostat, 1 =
Room thermostat zone 2
1
2
2
4
Automatic Temperature Control
0 = Disabled, 1 = Enabled
0
2
2
5
Heating ignition delay (for new demand)
0 = Disabled, 1 = 10 seconds, 2 =
90 seconds, 3 = 210 seconds
0
2
2
8
Combi Version -
WCN
Models
CANNOT BE MODIFIED
0 = Combi
0
Boiler Version -
WBN Models
Type of DHW control for Indirect Hot Water
Heater (Tank Sensor or Aquastat)
0 = NOT USED
1 = Storage with Tank Sensor
2 = Storage with Aquastat
2
2
2
9
Boiler Heating Capacity (MBH)
0 - 200
Only if the PCB is changed