LP-743 Rev. 000 Rel. 000 Date 8.25.20
17
M
enu
Sub
-M
enu
Par
amet
er
Description
Value
Default Setting
34 - 40 7
4
Floor drying cycle
0 = OFF
1 = Functional Heating
2 = Curing Heating
3 = Functional H Curing Heating
4 = Curing Heating + Functional Heating
5 = Manual
0
34 - 40 7
5
Floor dry Supply setpoint temperature
77 - 140°F
131
34 - 40 7
7
Burning Hours Harmonization
Sets the burner run hours statistics to equal the average of the other boilers in the cascade. Used when replacing the
PCB on a Follower boiler. Perform this function ONLY on the boiler where the PCB has just been replaced.
34 - 40 8 RESET MENU
34 - 40 8
0
Automatically resets all parameters to the
factory defaults.
WARNING:
Always check PCB settings
if restoring factory default settings on a
replacement controller. Replacement controllers
have generic settings that may not be specific to
the boiler model.
Reset: OK = yes,
ESC
= no
Only applicable to parameters in menu level 34-40 of respective Follower boiler.
34 - 40 10 OTHERS 2
34 - 40 10 0
NOT USED
34 - 40 10 1
DHW Modulation Setpoint
68 - 179
o
F
179
Boiler target temperature during a DHW demand. Not applicable for WCN models.
34 - 40 10 2
DHW On Differential Temperature
0 - 36
o
F
0
Determines how much the DHW storage tank temperature can drop below target before initiating a DHW demand. Only
applicable when 2.2.8 = 1.
34 - 40 10 3
Emergency Setpoint
68 - 179
o
F
113
Sets Follower boiler operating temperature when communication with the Master is lost, or when the System Sensor is
disconnected. See Cascade Instruction Manual.
34 - 40 10 4
NOT USED
34 - 40 10 5
NOT USED
34 - 40 10 6
NOT USED
34 - 40 50 BOILER STATISTICS - 1 - READ ONLY
34 - 40 50 0
3 way valve cycles No. (n x10)
34 - 40 50 1
Boiler Pump On Hours (h x10)
34 - 40 50 2
Boiler pump cycles No. (n x10)
34 - 40 50 3
Boiler Power On Time (h x10)
34 - 40 50 4
Fan On Hours (h x10)
34 - 40 50 5
Number of fan cycles (n x10)
34 - 40 50 6
CH number of flame detections (n x10)
34 - 40 50 7
DHW number of flame detections (n x10)
34 - 40 51 BOILER STATISTICS - 2 - READ ONLY
34 - 40 51 0
CH Burner On Hours (h x10)
34 - 40 51 1
DHW Burner On Hours (h x10)
34 - 40 51 2
Number Of Flame Faults (n x10)
34 - 40 51 3
Number Of Ignition Cycles (n x10)