LP-743 Rev. 000 Rel. 000 Date 8.25.20

11

C. Technical Menu - Cascade Master Menu Structure

The technical menu levels and parameter selection options for 

boilers configured as Master and Followers are different than those 

configured as standalone boilers. The differences are as follows:

Master Boiler

 – Retains the technical menu levels available in a 

standalone boiler while adding menu level 25 for parameters speci-

fic to Cascade Management. 

NOTE:

 Some parameters normally ac-

cessed via menu levels 2 and 8 for a single boiler are now accessed 

via the Cascade Management menu – see below:

•  Automatic Temperature Control moves from 2.2.4 to 25.1.0

•  Outdoor Temperature Reading Correction: from 2.4.9 to 

25.1.1

•  CH Boost Interval: from 2.4.4 to 25.1.2

Figure 21 - Menu Structure

0

NETWORK

25

Cascade Manager Parameters

4

User Interface

0

General

2

Boiler Parameters

1

System Settings

0 General

2

Domestic Hot Water

1 Free Parameters

3

System Diagnostics

2

Settings

4

Cascade Diagnostics

3 Central Heating-1

5

Error History

4 Central Heating-2

6

Reset Menu

5 Domestic Hot Water

34...40

Cascade Follower 1 - 7 Parameters

6 Boiler Manual Settings

0

General

7 Test & Utilities

1

Free Parameters 

8 Reset Factory Settings

2

Settings

4

Zone1 Parameters

3

Central Heating-1

0 Setpoint

4

Central Heating-2

1 S/W Changeover

5

Domestic Hot Water

2 Z1 Settings

6

Boiler Manual Settings

3 Z1 Diagnostics

7

Test & Utilities

7 Z1 Regulation parameters

8

Reset Factory Settings

5

Zone2 Parameters

9

Other-1

0 Setpoint

10

Other-2

1 S/W Changeover

11

Boiler Statistics-1

2 Z2  Settings

12

Boiler Statistics-2

3 Z2 Diagnostics

13

Boiler

7 Z2 Regulation parameters

14

Boiler Temperature

6

Zone3 Parameters

15

Storage

0 Setpoint

16

Service

1 S/W Changeover

17

Error History

2 Z3  Settings

18

Free Parameters

3 Z3 Diagnostics

42

BMS Parameters

7 Z3 Regulation parameters

0

General

8

Service Parameters

1

Analog Level Settings

0 Boiler Statistics -1

2

Diagnostics

1 Boiler Statistics -2
2

Boiler

3 Boiler Temperature
4 Storage
5 Service
6 Error History
7

Free parameters

8

Reset Factory Settings

9

Other - 1

10

Other - 2

11

HTP Zone Controller Parameters

0 General
1 Diagnostics

Quick Access Menus

PCB

 

Direct Access to the Parameters:

219, 220, 228, 229, 231 - 234, 247, 

253, 257 (only when parameter 228 

=1)

ERR

 - Fault

The display shows the last 10 errors 

with the code, description, and date.
Press “+” (2) to scroll through errors

MENU

Complete menu, with access to all 

parameters - see the following pages 

for details.

DHW

 - Domestic Hot Water settings

Direct Access to the Parameters:

228

CH1 - Heating 

Zone 1

 

settings

Direct Access to the Parameters:

420, 422, 423, 425, 426, 475

CH2- Heating 

Zone 2 

settings

Direct Access to the Parameters:

520, 522, 523, 525, 526, 575

CH3- Heating 

Zone 3 

settings

Direct Access to the Parameters:

620, 622, 623, 625, 626, 675

MODE - 

Boiler working MODE

Press “+” (2) to select:

 (Only DHW) - 
 

 (CH + DHW) -

 (Only CH)

BMS - Building Management 

System

 settings

Only applicable with 0-10V / 4-20mA 

Clip-In Board installed

•  DHW Setpoint Temperature: from 2.0.0 to 25.2.0

•  DHW Comfort Function: from 2.5.0 to 25.2.1

•  Anti-legionella Function: from 2.5.7 to 25.2.3

•  CH Supply Setpoint (diagnostic – read only): from 8.3.0 to 25.3.0

•  Outdoor Temperature (diagnostic – read only): from 8.3.5 to 

25.3.2

Follower Boiler 

– Retains technical menu level 0 for setting the boiler 

address. Loses menu levels 4, 5, and 6 normally used for managing CH 

settings (Followers do not manage CH), and moves menu levels 2 and 

8 to new menu level 34 (for Follower 1) [35-40 for Follower 2-7]. 

NOTE:

 The Master boiler also has access to the Follower menu of each 

Follower in the cascade system.

Содержание EFTU Series

Страница 1: ...er birth defects or other reproductive harm The surfaces of these products contacted by potable consumable water contain less than 0 25 lead by weight as required by the Safe Drinking Water Act Section 1417 Heat Exchanger Bears the ASME H Stamp This document is provided in addition to other documentation and DOES NOT REPLACE the installation manual This document must only be used by a qualified in...

Страница 2: ...tream of all closely spaced tees 4 The minimum individual boiler pipe size of DHW piping should be diameter and CH piping should be 1 in diameter 5 Circulators are shown with isolation flanges The alternative is standard flanges with full port ball valves Purge valves can be used with circulator flanges as an alternative 6 Piping shown is Primary Secondary 7 Install a minimum of 12 diameters of st...

Страница 3: ...NCTION BOX BUS T B 120V TT2 120V OD 5V IN 120V TNK 120V SYS 120V TT1 120V PCB CONTROL PANEL RT DHW PUMP CH PUMP 120VAC JUNCTION BOX OD OD MASTER FOLLOWER RT FOLLOWER DOWNSTREAM INDIRECT FIRED WATER HEATER UPSTREAM INDIRECT FIRED WATER HEATER Piping for Models ELU 85WBN 120WBN 120WCN 150WCN NOTICE In this plumbing application parameter 25 1 6 needs to be adjusted to setting 1 This ensures the CH pu...

Страница 4: ...PUMP CH PUMP 120VAC JUNCTION BOX RT DHW PUMP CH PUMP 120VAC JUNCTION BOX RT OD OD MASTER FOLLOWER FOLLOWER DHW PUMP CH PUMP 120VAC JUNCTION BOX DOWNSTREAM INDIRECT FIRED WATER HEATER UPSTREAM INDIRECT FIRED WATER HEATER Piping for Models ELU 150WBN 199WBN 199WCN EFTU 85WBN 110WBN 150WBN 199WBN 110WCN 150WCN 199WCN NOTICE In this plumbing application parameter 25 1 6 needs to be adjusted to setting...

Страница 5: ...ishing Boilers as Master and Followers procedure Menu level 25 is not accessible unless 0 4 6 is set to b MAS Parameter Description Value Default Setting 0 4 6 Cascade Boiler Address Master boiler must be set to b MAS UNDEF undefined b SIN single boiler b MAS master boiler b FL1 Follower 1 boiler b FL2 Follower 2 b FL3 Follower 3 b FL4 Follower 4 b FL5 Follower 5 b FL6 Follower 6 b FL7 Follower 7 ...

Страница 6: ...er Menu Refer to parameter 5 2 5 and 6 2 5 for CH Zone 2 and 3 4 2 6 Minimum CH Temperature Setting Zone 1 TT1 68 122 F when 4 2 0 0 86 179 F when 4 2 0 1 80 4 2 0 0 120 4 2 0 1 Sets the minimum allowable boiler operating temperature for CH Zone 1 limiting Automatic Temperature Control and manual adjustment from the User Menu Refer to parameter 5 2 6 and 6 2 6 for CH Zones 2 and 3 25 1 6 System CH...

Страница 7: ...ting Power 120V for DHW and CH Circulators NOTE TheCHanddownstreamIWHcirculatorsMUSTBECONNECTED to the Master Boiler to ensure proper operation To connect power for the CH and DHW external pump at the boiler junction box 1 Shut off the power supply at the boiler and at the circuit breaker 2 Shut off the gas at the manual shutoff 3 Remove the boiler front cover 4 Disconnect the three clips and open...

Страница 8: ... allow Automatic CH Temperature Control or connect Master boiler to WiFi and use Internet Weather TNK Tank Sensor or Aquastat Connect to a tank sensor or Aquastat installed in a Downstream IWH heated by the entire cascade system and set via 25 2 2 Or installed in an Upstream IWH connected to the Master boiler and set via 2 2 8 NOTE The Master boiler cannot heat both a Downstream and an Upstream IW...

Страница 9: ...by Boiler Supply Sensor Master Homescreen 3 Boiler Supply Temperature This screen displays the current temperature read by the master boiler supply sensor 150oF is displayed below Figure 11 Master Homescreen 3 Boiler Off This screen displays if the master boiler is turned off with the ON OFF button Master Homescreen 4 Cascade Master Operating Power Level This screen displays the current operating ...

Страница 10: ...iler Operating Power Level This screen displays the current operating power level percentage of the follower boiler A power level of 40 is displayed below PL Denotes Boiler Power Level Current Power Level Percentage Figure 18 Follower Homescreen 3 Boiler Power Level Follower Homescreen 4 Indirect Water Heater Tank Temperature Aquastat Status of Upstream Local IWH This screen is only displayed on t...

Страница 11: ...0 Setpoint 16 Service 1 S W Changeover 17 Error History 2 Z3 Settings 18 Free Parameters 3 Z3 Diagnostics 42 BMS Parameters 7 Z3 Regulation parameters 0 General 8 Service Parameters 1 Analog Level Settings 0 Boiler Statistics 1 2 Diagnostics 1 Boiler Statistics 2 2 Boiler 3 Boiler Temperature 4 Storage 5 Service 6 Error History 7 Free parameters 8 Reset Factory Settings 9 Other 1 10 Other 2 11 HTP...

Страница 12: ...ctory Settings 9 Other 1 10 Other 2 11 Boiler Statistics 1 12 Boiler Statistics 2 13 Boiler 14 Boiler Temperature 15 Storage 16 Service 17 Error History 18 Free Parameters 19 20 28 29 31 32 33 34 47 53 Boiler Temperature Quick Access Menus PCB Direct Access to the Parameters 34 40 19 34 40 20 34 40 28 34 40 29 34 40 31 34 34 40 47 34 40 53 ERR Fault The display shows the last 10 errors with the co...

Страница 13: ...void short cycling ensure 25 0 4 is set to less than half of 25 0 5 setting Applicable only when parameter 25 0 2 0 25 0 5 Cascade Manager Max Turnover Level par 25 0 4 100 70 Sets the power level threshold where the next boiler is switched on Switches on if required power is 25 0 5 Switches off if required power is 25 0 5 25 0 3 Off logic only applicable if parameter 25 0 2 1 25 0 7 CH On Differe...

Страница 14: ... and CH will not operate simultaneously Priority switches between DHW and CH at an interval de fined by the CH DHW Shifting Priority Time parameter 25 0 8 first priority is DHW If 25 0 8 0 then DHW has priority indefinitely 1 Timed Concurrent Alternating DHW and CH operate simultaneously for the period defined by the CH DHW Shi fting Priority Time parameter 25 0 8 After the time elapses operation ...

Страница 15: ...LER 1 7 34 40 0 GENERAL 34 40 0 1 DHW Preheating 0 Disabled 1 Enabled 1 Enables disables DHW Comfort Function on WCN models not applicable to WBN models See par 25 2 1 34 40 1 FREE PARAMETER 34 40 1 9 DHW Flow Detection Device Type 0 Flow Switch 1 Flow Meter Varies Default 0 for TRX085 120 110C 150C Default 1 for TRX150 199 199C FTVN085 110 150 199 110C 150C 199C WCN models use a flow meter Not ap...

Страница 16: ...ring 34 40 5 3 DHW Switch Off Logic 0 anti scale stop at 144 F 1 7 F setting 0 34 40 5 4 DHW Post Purge and Pump Cycle 0 OFF 1 ON 1 OFF 30secondpost circulationand2minutepost ventilation or3minutepost circulationand5minutepost ventilation if the boiler temperature requires it ON When setting is ON time for post circulation is 3 minutes while the time for post ventilation is 5 minutes Default 0 for...

Страница 17: ...40 10 OTHERS 2 34 40 10 0 NOT USED 34 40 10 1 DHW Modulation Setpoint 68 179oF 179 Boiler target temperature during a DHW demand Not applicable for WCN models 34 40 10 2 DHW On Differential Temperature 0 36oF 0 Determines how much the DHW storage tank temperature can drop below target before initiating a DHW demand Only applicable when 2 2 8 1 34 40 10 3 Emergency Setpoint 68 179oF 113 Sets Follow...

Страница 18: ...xt maintenance 0 60 months 12 If enabled 8 5 1 1 a notification is made on the display and via the Tele diagnostic Service if applicable warning that it is time for maintenance 34 40 55 1 Enable Maintenance Warning 0 OFF 1 ON 0 34 40 55 2 Maintenance Warning Reset Reset OK Yes Esc No Resets Maintenance Advice and clears the Warning 34 40 55 4 SW Version Display Interface 34 40 55 5 SW Version Main...

Страница 19: ...address Press OK again 2 If above process does not work access parameter 0 4 6 and set the correct boiler address see Cascade Control Set Up Blocking Auto Reset EMERG Emergency Mode 1 The Follower has been disconnected from the BUS or no longer sees the Master on the BUS check the BUS connections See Wiring a Cascade System 2 The control has sensed a short circuit on the BUS connection Disconnect ...

Страница 20: ...LP 743 Rev 000 Rel 000 Date 8 25 20 20 Maintenance Notes ...

Отзывы: