FULLTEST
3
EN - 40
5.7.3. R
A
MEASUREMENT
Measured quantities and display ranges:
Global earth resistance R
A
0
2.000
(
I
N
= 10 or 30 mA)
0
1.000
(
I
N
= 100 mA)
0
300
(
I
N
= 300 mA)
0
200
(
I
N
= 500 mA)
0
150
(
I
N
= 650 mA)
0
100
(
I
N
= 1000 mA)
Mains voltage U
L/PE
100
265 V AC
Contact voltage U
C
0
100 V AC (U
C LIM
= 50 V)
0
50 V AC (U
C LIM
= 25 V)
Input requirements:
Mains voltage U
L/PE
(READY condition) 100
265 V AC
1)
Select the R
A
measurement by pressing the
FUNC
hard key first.
2)
Check selected nominal differential current (10, 30, 100, 300, 500, 650 and 1000 mA) and modify it
if needed by pressing the
I
N
(6) touch-screen key first.
3)
Select measurement screen by pressing the
(5) touch-screen key and check all settings again.
4)
Connect the test leads according to one of the figures below. READY message (3) will appear
when mains voltage U
L/PE
within 100 ... 265 V is present.
Figure 29: Connection of test cable to schuko socket
Figure 30: Connection of test leads to tested wiring