August-2015
Page 9
3.3.4.
Fire function keys
HST-HP201-2 contains 5 fire functions keys used to perform all fire related actions.
Triggering any fire function key is under level 2 access except Silence Buzzer key which is
under level 1 access.
Silence Buzzer key: Used to silnece panel buzzer after fire or fault condition.
Silence Alarm key: Used to silence on board relays, on borad sounders and loop
output devices after fire condition.
Resound Alarm key: Used to resound the silenced onboard, relays, on borad sounders
and loop output devices after fire codition.
Reset key: Used to perform panel reset after fire or fault condition. All onboard and
loop modules will return to its default state. In case that condition which caused the
fire or fault is still active, panel will change its state again according to the active
event.
Evacuate key: Used to perform manual evacuate action.
3.3.5.
General function keys
HST-HP201-2 contains 2 onboard general function keys which can be programmed
independently to perform one of several functions. Triggering any function key is under level
2 access. By default keys are not programmed so there will be no effect when pressed. Keys
can be programmed from panel configuration menus or from computer software.
3.3.6.
Test key
HST-HP201-2 contains one Test key which is used to start LCD & LEDs test for 2
seconds. LCD will draw HST Logo and all Icons in an inverted way and all LEDs will be
turned on.