6.1.1.3.
Menu3: Loops configuration
This menus consists of 6 menu items
1.
Loops status
To select this item use arrow keys to highlight it and press ENTER key or press 1 key
from numeric keypad.
This menu is used to display information about loops status and number of devices
connected to it. First line displays total number of connected devices for all loops then total
number of inputs devices for all loops (detectors, call point, …) then total number of output
devices for all loops (output modules, loop sounders, …).
After that loops are displayed line by line. Same information for devices is displayed but
for each loop only.
At the end of each loop line, if there is ! Symbol, it means that this loop has at least one
loop fault. If there is X symbol, it means that this loop is disabled and not working.