Figure 1. Wiring diagram:

Warning

Forbid  connect  24VDC  directly   without  current-limiting

resistance. Otherwise, the detector would be burnt out.

Dust covers are an effective way to limit the entry of
dust into smoke detector sensing chambers. However,
they   may   not   completely   prevent   airborne   dust
particles   from   entering   the   detector.   Therefore,   We
recommends   the   removal   of   detectors   before
beginning   construction   or   other   dust   producing
activity.
Be sure to remove the dust covers from any sensors
that were left in place during construction as part of
returning the system to service.

TAMPER-RESISTANCE

Models DG311 include a tamper-resistant capability that
prevents their removal from the bracket without the use
of a tool.

TESTING

Before   testing,   notify   the   proper   authorities   that   the
smoke   detector   system   is   undergoing   maintenance   and
will temporarily be out of service. Disable the zone or
system   undergoing   maintenance   to   prevent   unwanted
alarms. Detectors must be tested after installation and as
part of periodic maintenance. 

NOTE:

  Before testing the detector, check to ensure the

LEDs blink. If they do not, the detector has lost power
(check the wiring), it is defective (return it for repair), or
the detector sensitivity is outside the listed limits.
The sensor can be tested in the following ways:

A. Smoke Entry test: Aerosol Generator (Gemini 501)
The GEMINI model 501 aerosol generator can be used
for   smoke   entry   testing.   Set   the   generator   to   represent
4%/ft to 5%/ft obscuration as described in the GEMINI
501   manual.   Using   the   bowl   shaped   applicator,   apply
aerosol until the panel alarms.
B.Direct Heat Method (Hair dryer of 1000 – 1500 watts)
1. From the side of the detector, direct the heat toward the
sensor. Hold the heat source about 6 inches (15cm) away
to prevent damage to the cover during testing.

A sensor that fails any of these tests should be cleaned as
described under CLEANING, and retested. If the sensor
fails after cleaning, it must be replaced.
When testing is complete, restore the system to normal
operation and notify the proper authorities that the system
is back in operation.

CLEANING

Before   removing   the   detector,   notify   the   proper
authorities that the smoke detector system is undergoing
maintenance   and   will   be   temporarily   out   of   service.
Disable the zone or system undergoing maintenance to
prevent unwanted alarms.

1. Remove the sensor to be cleaned from the system.
2. Remove the sensor cover by pressing firmly on each

of the four removal tabs that hold the cover in place.

3. Vacuum the screen carefully without removing it. If

further   cleaning   is   required   continue   with   Step   4,
otherwise skip to Step 7.

4. Remove   the   chamber   cover/screen   assembly   by

pulling it straight out.

5. Use a vacuum cleaner or compressed air to remove

dust and debris from the sensing chamber.

6. Reinstall   the   chamber   cover/screen   assembly   by

sliding the edge over the sensing chamber. Turn until
it is firmly in place.

7. Replace the cover using the LEDs to align the cover

and then gently pushing it until it locks into place. 

8. Reinstall the detector.
9. Test the detector as described in TESTING.
10. Reconnect disabled circuits.
11. Notify the proper authorities that the system is back

on line.