5.1.6.1 Mounting the electrode
NOTICE
Broken electrode pins
If too much force is exerted during mounting, the pins on the electrode may break off.
► Always mount the electrode carefully, never use excessive force.
► Place the electrode opposite the electrode holder so that the pins are located opposite the
openings in the disc.
The openings in the disc on the electrode holder are arranged asymmetrically in
order to prevent incorrect mounting of the electrode.
► Turn the electrode until it can be mounted.
► Guide the electrode into the electrode holder.
► Engage the electrode with a sharp rotation to the right.
5.1.7 Cleaning the bushing
► Clean the bottom end of the bushing with ethyl acetate.
5.2
Mounting the bushing on the transformer
► Observe the transformer manual for mounting the bushing on the transformer (including
sealing the bushing and tightening the fixing screws).
5.2.1 Slinging the bushing for installation
► If the bushing is resting on the bearing supports and is no longer slung, then sling it again
on page 20).
5.2.2 Putting the bushing at an inclination
► Lift the bushing.
Range STARIS®-Sia+