Shenzhen Hpmont Technology Co., Ltd.
Chapter 6 Function Introduction
HD3Z Series User Manual V1.2
-37-
Ref. Code
Function Description
Setting Range [Default]
F04.20
Proportional gain (P2)
0.0 - 100.0 [50.0]
F04.21
Integral time (I2)
0.01 - 10.00 [1.00s]
F04.22
Differential time (D2)
0.00 - 10.00 [0.00s]
F04.23
PID parameter adjustment bases
0 - 3 [0]
0: Do not adjust. Second PID is invalid.
1: DI.
•
Switch PID parameter according to DI terminal No.59 function. When the terminal is invalid, select
group 1 (F04.04, F04.05, F04.07); When valid, select group 2 (F04.20 - F04.22).
2: Bias.
•
Select group 2 when bias between PID feedback and PID setting < PID parameter switching point 1
(F04.24).
•
Select group 1 when bias between PID feedback and PID setting > PID parameter switching point 1
(F04.25).
•
Select linear interpolation when bias between PID feedback and PID setting is within switching point 1
and 2.
3: Frequency.
•
Select group 1 when PID output frequency < switching point 1 (F04.24);
•
Select group 2 when PID output frequency > switching point 2 (F04.25);
•
Select linear interpolation when PID output frequency is within switching point 1 and 2.
F04.24
PID parameter switching point 1
0.0 - F04.25 [0.0%]
F04.25
PID parameter switching point 2
F04.24 - 100.0 [100.0%]
F04.29
PID calculating mode
0,1 [0]
0: Do not calculate when HD3Z stops.
1: Calculate when HD3Z stops.
F04.30
PID dormancy selection
0,1 [0]
0: Disable.
1: Enable.
F04.31
Wakeup tolerance
0.0 - 100.0 [10.0%]
F04.32
Wakeup delay
0.0 - 6000.0 [0.0s]
Positive: In dormant status, when feedback ≤ setting × (100% - F04.31), and counting time ≥ F04.32, wake
up HD3Z.
Negative: In dormant status, when feedback ≥ setting × (100% + F04.31), and counting time ≥ F04.32, wake
up HD3Z.
F04.33
Dormancy tolerance
0.0 - 100.0 [10.0%]
F04.34
Dormancy delay
0.0 - 6000.0 [0.0s]
F04.35
Dormancy frequency
0.00 -Max. frequency
[20.00Hz]
Positive: In wakeup status, when feedback ≥ setting × (100% + F04.33), target frequency ≤ F04.35 and
counting time ≥ F04.34, HD3Z is dormant.
Negative: In wakeup status, when feedback ≤ setting × (100% - F04.33), target frequency ≤ F04.35 and
counting time ≥ F04.34, HD3Z is dormant.
6
Содержание HD3Z Series
Страница 1: ...V1 2 2018 11 HD3Z Series Mining Inverter User Manual HD3Z Series Mining Inverter...
Страница 3: ......
Страница 4: ...Version and Revision Records Time 2018 11 Version V1 2 Revised chapter Revised contents V1 2 published...
Страница 5: ......
Страница 11: ......
Страница 15: ......
Страница 17: ......
Страница 83: ......