Shenzhen Hpmont Technology Co., Ltd.
Chapter 10 Parameter
HD09 Series User Manual V1.1
-73-
Ref. Code
Function
Setting Range
Default
Unit
Attribute Setting
F02: Start and Stop Controlling Parameter
F02.02
Start DWELL frequency
setting
0.0 - F00.08
0.0Hz
0.1Hz
×
F02.03
Retention time of starting
DWELL frequency
0.00 - 10.00s
0.00s
0.01s
×
F02.04
DC braking current setting
0 - 100%
50%
1%
×
F02.05
DC braking time at start
0.00 - 60.00s
0.00s
0.01s
×
F02.13
Stop mode selection
1: Coast to stop
2: Decelerate to stop
2
1
×
F02.14
DWELL frequency setting
at stop
0.0 - F00.08
0.0Hz
0.1Hz
×
F02.15
Retention time of DWELL
frequency at stop
0.00 - 10.00s
0.00s
0.01s
×
F02.16
DC braking initial
frequency at stop
0.0 - 50.0Hz
0.5Hz
0.1Hz
×
F02.18
DC braking time at stop
0.00 - 60.00s
0.00s
0.01s
×
F03: Acceleration and Deceleration Parameter
F03.01
Acceleration time 1
0.01 - 600.00s
10.00s
0.01s
○
F03.02
Deceleration time 1
0.01 - 600.00s
10.00s
0.01s
○
F03.03
Acceleration time 2
0.01 - 600.00s
10.00s
0.01s
○
F03.04
Deceleration time 2
0.01 - 600.00s
10.00s
0.01s
○
F03.05
Acceleration time 3
0.01 - 600.00s
10.00s
0.01s
○
F03.06
Deceleration time 3
0.01 - 600.00s
10.00s
0.01s
○
F03.07
Acceleration time 4
0.01 - 600.00s
10.00s
0.01s
○
F03.08
Deceleration time 4
0.01 - 600.00s
10.00s
0.01s
○
F03.09
Ace. time 2 and 1 switch
frequency
0.0 - up limitation
0.0Hz
0.0Hz
×
F03.10
Dec. time 2 and 1 switch
frequency
0.0 - up limitation
0.0Hz
0.0Hz
×
F03.15
Spot Ace. time
0.01 - 600.00s
6.00s
0.01s
○
F03.16
Spot Dec. time
0.01 - 600.00s
6.00s
0.01s
○
F04: Process PID Controlling Parameter
F04.00
Process PID control
selection
0: PID control is disabled
1: PID control is enabled
0
1
×
F04.02
Feedback source selection
0: AI analogue feedback
1: Terminal pulse feedback
0
1
×