Shenzhen Hpmont Technology Co., Ltd.
Chapter 5 Technical Data
HD09 Series User Manual V1.1
-19-
Chapter 5
Technical Data
5.1
Peripheral Accessories Selection
5.1.1
Wiring Specifications of Input and Output
The AC supply to the drive must be installed with suitable protection against overload and short-
circuits, i.e. MCCB (molded case circuit breaker) or equivalent device.
The recommended specification of MCCB, contactor & cables were shown as following tables.
The size of earth wire should not be smaller than the requirement in 4.3.5.4 of IEC61800-5-1.
Size
Model
MCCB
(A)
Contactor
(A)
Power Cable
(mm
2
)
Motor Cable
(mm
2
)
Ground
Cable (mm
2
)
Size A
HD09-2S0P2G
16
10
0.5
0.2
2.5
Size A
HD09-2S0P4G
16
10
0.75
0.5
2.5
Size A
HD09-2S0P7G
16
10
2.5
0.5
2.5
Size A
HD09-2S1P5G
20
16
6.0
1.5
6.0
Size A
HD09-2S2P2G
32
20
6.0
2.5
6.0
Size A
HD09-4T0P4G
10
10
0.5
0.2
2.5
Size A
HD09-4T0P7G
10
10
0.5
0.5
2.5
Size A
HD09-4T1P5G
16
10
1.0
0.5
2.5
Size A
HD09-4T2P2G
16
10
1.5
0.75
2.5
Size B
HD09-4T4P0G
25
16
2.5
2.5
2.5
Size B
HD09-4T5P5G
32
25
4.0
4.0
4.0
Note:
1. Please select braking resistor based on the above table.
Bigger resistor can protect the braking system in fault condition, but oversized resistor may bring a
capacity decrease, lead to over voltage protection.
2. The braking resistor should be mounted in a ventilated metal housing to prevent inadevertent contact
during it works, for the temperature is high.