Chapter 7 Detailed Function Introduction
HD09 Series User Manual V1.1
-27-
Chapter 7
Detailed Function Introduction
7.1
F00: Basic Parameter
Ref. Code
Function Description
Setting Range [Default]
F00.06
Max.output frequency
50.0 - 1000.0 [50.0Hz]
Define converter max. permissible output frequency.
•
Shall be setted reasonably in according with motor nameplate and actual running situation.
F00.08
Maximum operating frequency
0.0 - F00.06 [50.0Hz]
F00.09
Minimum operating frequency
0.0 - Max.frequency [0.0Hz]
F00.10
Frequency setting access selection
0 - 4 [0]
0: Keypad digital setting.
1: Terminal digital setting.
2: SCI communication setting.
3: Analogue setting.
4: Terminal impulse setting.
F00.11
Operation command access selection
0 - 2 [0]
0: Keypad operation command
1: Terminal operation command.
2: SCI communication command.
F00.13
Original operation frequency digital setting
0.0 - Max.frequency [50.0Hz]
F00.14
Frequency setting control
0000 - 1111 [1001]
Enable only when F00.10 = 0,1.
When F00.13 is changed, the new value will replace current setted frequency.
Units: Selection of frequency save when power off
•
0: No.
•
1: Save.
Tens: Setted frequency when stopping
•
0: Keep setted frequency in stopping
•
1: Recover to F00.13 in stopping.
Hundreds: Selection of frequency save when
communicating
•
0: No.
•
1: Save.
Thousands: Selection of frequency save when
change frequency access
•
0: No.
•
1: Save.When frequency setted access is changed
from keypad to terminal digital and back to
keypad, the keypad frequency is still keeping the
last changed frequency.
F00.15
Inching operation frequency digital setting
0.0 - Max. frequency [5.0Hz]