Understanding the controls

Adjusting the duration time

The length of time that the unit remains switched on after activation can 
be adjusted from 10±5 seconds to 4±1 minutes. Rotating the TIME knob 
anticlockwise from (+) to(-) reduces the duration time. Note: Once the light 
has been triggered by the PIR sensor any subsequent detection will start 
the timed period again from the beginning.

Adjusting the LUX control level

The LUX control module has a built-in sensing device (photocell) that 
detects daylight and darkness. Rotate the LUX knob anticlockwise from 
light ( ) to dark ( ). The ( ) position will allow the floodlight to work day 
and night, and the ( ) position works only at night. You can set the unit to 
operate at the desired level by adjusting the LUX knob.

Adjusting Sensing Distance

Rotating the SEN knob anti clockwise from (+) to (-) reduces the sensing 
distance. (Refer Fig. 2)

Cat no.

LSS0112WBL

LSS0125WBL

Supply voltage

230-240V a.c. 50Hz

Input power

14W

29W

Power output

12W

25W

Lumens output

1070lm

2200lm

Colour 
temperature

Cool white 4000K nominal

Mounting height

2m (recommended)

Protection class

Class 1

Weatherproof 
rating

IP44

Size (mm)

240 x 120 x 180 mm

170 x 240 x 180 mm

Weight  
(excl packaging)

0.7kg

1.1kg

Power cord 
requirement

H05RN-F 3G 1mm

2

PIR sensor

Standby power

1.0W

Detection range

12m (max), 180° scan

Time adjustment

10 ±5 sec to 4 ±1 min

Switching function

Auto mode / Manual override

Setting the controls

 

With floodlight fully installed by electrician and  

power on

1.  Turn the LUX control knob to light ( ) position, turn the wall switch on 

and wait 30 seconds for the control circuit to stabilise. Ensure the TIME 
control knob is set at minimum (-).The lamp on the sensor light will now 
switch on and will remain on for about 1 minute.

2.  Direct the sensor toward the desired scanning area by adjusting the 

elbow joint and swivel joint on the sensor arm. Important: loosen all 
lock nuts and screws on sensor arm before making any adjustments.

3.  Have someone move across the centre of the area to be scanned and 

slowly adjust the angle of the sensor arm until the unit senses the moving 
person, causing the lamp to switch on. (Refer Fig.1 B)

4.  Adjust time control to required setting.

5.  To set the light level at which the lamp will automatically switch “On”, 

turn the LUX control knob from daylight to night. If the lamp is required 
to switch on earlier, e.g. dusk, wait for the desired light level, then 
slowly turn the LUX control knob towards daylight while someone 
walks across the centre of the area to be detected. When the lamp 
switches on, release the LUX knob. You may need to make further 
adjustments to achieve your ideal light level setting.

Important: To avoid dust build-up and ensure proper functioning of 
the sensor light, wipe the sensor lens lightly with a damp cloth every 
3 months. Never modify the unit, there are no user serviceable parts 
inside.

Dial settings show  

TEST MODE

Fig. 5

POWER ON

1

2

3

AUTO MODE

MANUAL MODE

How to change into manual control mode

1.  When power is first switched on,the PIR detector enters into the 

WARM-UP period for about 1 minute, then automatically changes 
into AUTO MODE.

2.  During AUTO MODE, by switching the ON/OFF main switch off & 

on twice in about 3 seconds, the PIR detector will automatically 
change into MANUAL MODE. In MANUAL MODE, the flood light will 
remain ON for 8 hours. It will not be affected by duration time and 
Lux control level. After 8 hours, the PIR detector will change back to 
AUTO MODE.

3.  During MANUAL MODE, by switching the ON/OFF main switch off 

& on twice in about 3 seconds, the PIR detector will automatically 
change into AUTO MODE. 

4.  During AUTO MODE or MANUAL MODE, by switching off the ON/

OFF main switch  over 10 seconds and then on again, the PIR 
detector will reset to WARM-UP period.

 

Specifications