Power
ProLiant SL210tGen8 Fully Configured
115V/60Hz
220V/50Hz
Fully Loaded System Input Wattage
(W)
651
638
Fully Loaded System Input Current
(A rms)
5.7
3.0
Fully Loaded System Thermal
(BTU- Hr)
2218
2174
Fully Loaded System VA
(Volt-Amp)
657
657
System Leakage with all power supplies loaded
(mA)
1.58
3.03
System Inrush Current with all power supplies
loaded
(A)
19
37
Power cord requirements
Nema 5-15P to IEC320-C13
IEC320-C13 to IEC320-C14
NOTE:
Power shown is for a fully configured system consisting of (2) CPUs, (16) DIMMs, (2) HDDs, and (1) PCI card per node.
Power Cord
AF556A
Server Power Cords
One 6' Highline (IEC-IEC) power cord ships standard
NOTE:
ProLiant SL servers are primarily connected to PDU's in data center racks so they ship standard with
only a PDU power cord (416151-B21).
NOTE:
If customers require a power cord, they can check the power cord matrix for the appropriate cord.
Please see the following power cord matrix:
http://www.hp.com/go/powercordmatrix
.
QuickSpecs
HP SL2500 Scalable System
System Specifications
DA - 14656 North America — Version 6 — December 9, 2013
Page 42