Chapter 5
Removing and Installing HP Rack Storage/12 Components
43
Replacing the Hot-Swap Management Board
The Management Board can be replace without affecting the operation of, or
access to, the disk arrays. The current HP Rack Storage/12 configuration is stored
in memory. When the replacement Management Board is installed, the current
operating configuration is unchanged. The configuration can be changed by
resetting the configuration switches and recycling AC power.
Preparing the Replacement Management Board
1. Remove the Management Board from its anti-static container (see
Figure 5-8).
Thumbscrews
Configuration Switches
Figure 5-8. Replacing the Management Board
2. Set the configuration switches on the replacement Management Board to
the settings on the Management Board currently installed in the HP Rack
Storage/12.