Chapter 3
Installing the HP Rack Storage/12 in a Rack
22
Installing the Chassis
Install the chassis and secure it to the support rails.
WARNING
Extend the anti-tip foot from the front of the rack and lower
all leveler feet to stabilize the rack before mounting rack
components. Failure to use the anti-tip foot and leveler feet
could result in injury.
1. Extend the anti-tip foot from the front of the rack and lower all leveler
feet to stabilize the rack.
WARNING
Two persons are recommended to lift the HP Rack Storage/12
chassis. The chassis weighs 35 pounds (15.9 Kg) with the
power supplies removed. Installing the chassis without
assistance could result in injury to the installer.
2. Remove the power supply from the chassis to reduce the lifting weight.
NOTE
The chassis top is wider than the bottom. The chassis top rests
on the support rails mounted in the rack.
3. Lift the chassis until the chassis top is above the support rails. Rest the
rear of the chassis on the support rails. Slide the chassis on the rails until
the chassis stops.
4. Secure the chassis to the support rails with two thumbscrews attached to
the rails.