UPS operations 34
1.
Initiate a REPO by closing the REPO contact.
CAUTION:
If the polarity is reversed while connecting the REPO port, the UPS powers up
normally.
2.
Verify proper connection of the REPO port:
a.
Power up the UPS by pressing the Power button.
b.
Disconnect the REPO port.
c.
Reconnect the REPO port.
If the polarity is correct, the REPO connectors can be disconnected, and then reconnected, without
initiating a REPO.
d.
Verify that the UPS remains in Operate mode (on page
31
).
e.
If a REPO is initiated, the polarity is reversed. Check and correct the connections.
Powering down the UPS
1.
Shut down all load devices.
2.
Switch the load segment circuit breakers the OFF position.
3.
Press and hold the
Power
button for 3 seconds. Power is removed from the load segments and the
ON/OFF button blinks.