Specifications 95
CAUTION:
To reduce the risk of electric shock or energy hazards:
•
This equipment must be installed by trained service personnel, as defined by the NEC and IEC
60950-1, Second Edition, the standard for Safety of Information Technology Equipment.
•
Connect the equipment to a reliably grounded SELV source. An SELV source is a secondary
circuit that is designed so normal and single fault conditions do not cause the voltages to
exceed a safe level (60 V DC).
•
The branch circuit overcurrent protection must be rated 24 A.
HP 1200 W CS Platinum Plus Hot-plug Power Supply (94%
efficiency)
Specification
Value
Input requirements
—
Rated input voltage
100 V AC
110 V AC to 120 V AC
200 V AC to 240 V AC
Rated input frequency
50 Hz to 60 Hz
Rated input current
9.1 A at 100 V AC
8.6 A at 110 V AC
6.7 A at 200 V AC
Maximum rated input power
897 W at 100 V AC input
1321 W at 200 V AC input
BTU per hour
3061 at 100 V AC input
4506 at 200 V AC input
Power supply output
—
Rated steady-state power
800 W at 100 V AC input
900 W at 120 V AC input
1200 W at 200 V to 240 V AC
input
Maximum peak power
800 W at 100 V AC input
900 W at 120 V AC input
1200 W at 200 V to 240 V AC
input
Hot-plug power supply calculations
For hot-plug power supply specifications and calculators to determine electrical and heat loading for the
server, see the HP Power Advisor website (
http://www.hp.com/go/hppoweradvisor
).