Configuring the HP Moonshot System  42 

For detailed configuration information, see the 

Switch Administrator's Guide

 and 

Switch CLI Guide 

in the HP 

Moonshot Information Library  

Access the CLI locally 

To access the CLI interface locally: 

1.

 

Use a console cable to connect a PC or terminal to the serial console port on the uplink module. 

2.

 

Configure the terminal with the following settings: 

o

 

115200 baud rate 

o

 

8 data bits 

o

 

No parity 

o

 

1 stop bit 

o

 

No flow control 

3.

 

Start the terminal. 
The switch login prompt appears. 

4.

 

Enter:

 admin

 

No password is set by default. 

 

Obtain the switch management IP address 

To access the switch console remotely, the iLO CM management port must be connected to a network. 
If DHCP services are provided on the network, obtain the switch management IP address: 

1.

 

Access the switch CLI interface locally. 

2.

 

Enter privileged exec mode. At the switch prompt, enter: 

enable

 

3.

 

Show the switch management IP address. At the privileged exec prompt, enter: 

show serviceport

 

If DHCP services are not available, configure the serviceport IP address. 
Be sure to configure the enable password before managing the switch remotely. 
To configure the switch, see the 

Switch Administrator's Guide

 and the 

Switch CLI Command Reference 

in the 

HP Moonshot Information Library  

Configure the Enable password 

The Enable password controls access to the privileged exec mode. The default authentication profile denies 
remote access to the privileged exec mode if the Enable password is not configured. Configure the Enable 
password before starting a remote session. 
To configure the password: 

1.

 

Access the CLI locally (on page 

42

). 

2.

 

To access the privileged exec mode, enter the following command:  

enable 

No password prompt appears if a password is not configured. 

3.

 

To configure the Enable password, enter the following command:  

Содержание Moonshot 1500

Страница 1: ... information for the HP Moonshot System This document is for the person who installs administers and troubleshoots the HP Moonshot System HP assumes you are qualified in the servicing of computer equipment and trained in recognizing hazards in products with hazardous energy levels Part Number 711993 004 June 2014 Edition 4 ...

Страница 2: ...products and services are set forth in the express warranty statements accompanying such products and services Nothing herein should be construed as constituting an additional warranty HP shall not be liable for technical or editorial errors or omissions contained herein Microsoft and Windows are U S registered trademarks of the Microsoft group of companies ...

Страница 3: ...y identification 13 Moonshot 6SFP Uplink Module components 13 Moonshot 6SFP Uplink Module LEDs and buttons 14 Moonshot 4QSFP Uplink Module components 15 Moonshot 4QSFP Uplink Module LEDs and buttons 15 HP Moonshot 1500 Chassis Management module components 16 HP Moonshot 1500 Chassis Management module LEDs and buttons 17 Chassis internal components 17 Cartridge slot and switch module bay identifica...

Страница 4: ... 44 Configuring a power cap 44 Troubleshooting 46 Troubleshooting resources 46 Regulatory information 47 Safety and regulatory compliance 47 Belarus Kazakhstan Russia marking 47 Turkey RoHS material content declaration 48 Ukraine RoHS material content declaration 48 Warranty information 48 Communications interference 48 Electrostatic discharge 49 Preventing electrostatic discharge 49 Grounding met...

Страница 5: ...em software components using HP Moonshot Component Pack HP Moonshot Component Pack is a comprehensive firmware solution tested on the HP Moonshot System and delivered as a compressed file The compressed file includes all the component files needed to update a Moonshot System Users deploy the firmware updates contained in the Moonshot Component Pack from a command line by using the iLO Chassis Mana...

Страница 6: ...cess HP APM see the HP ProLiant SL Advanced Power Manager User Guide in the HP Moonshot Information Library http www hp com go moonshot docs Hot plug power supply calculations For hot plug power supply specifications and calculators to determine electrical and heat loading for the HP Moonshot System see the HP Power Advisor on the HP website http www hp com go hppoweradvisor Compiling the document...

Страница 7: ...install the chassis starting from the bottom of the rack and then work your way up the rack WARNING To reduce the risk of personal injury from hot surfaces allow the drives and the internal system components to cool before touching them WARNING To reduce the risk of electric shock or damage to the equipment Never reach inside the chassis while the system is powered up Perform service on system com...

Страница 8: ...ch piece of equipment before installation CAUTION To reduce the risk of damage to the equipment when installing third party options Do not permit optional equipment to impede airflow around the chassis or to increase the internal rack temperature beyond the maximum allowable limits Do not exceed the manufacturer s TMRA Grounding requirements This equipment must be grounded properly for proper oper...

Страница 9: ... Chassis 2 Cartridges 3 Cartridge blank 4 Access panel 5 Switch module 6 Fans 5 7 Uplink module 8 Moonshot 1500 CM module 9 Power supplies The quantity depends on the configuration ordered The following documents also ship with the Moonshot System Start Here for Important Setup Information Safety Compliance and Warranty Information ...

Страница 10: ...Description LED Status 1 Chassis power LED Flashing Green The chassis is waiting to power on Green Normal operation Amber Standby operation Off No power 2 Chassis health LED Green Normal operation Flashing Amber Degraded condition Flashing Red Critical condition Off No power 3 Chassis UID LED button Blue Chassis ID is selected Flashing blue System firmware update is in process Off Chassis ID is no...

Страница 11: ...itch module A health LED Green Normal operation Flashing Amber Degraded condition Flashing Red Critical condition Off Switch module is not installed or no power exists 6 Switch module B health LED Green Normal operation Flashing Amber Degraded condition Flashing Red Critical condition Off Switch module is not installed or no power exists Chassis rear panel components Item Description 1 Fans 5 2 Mo...

Страница 12: ...Identifying components and LEDs 12 Fan bay numbering Fan LED Status Description Off The fan is working or the power is off Solid amber The fan has failed Power supply bay numbering ...

Страница 13: ...r to power supply units Check the AC power cord AC is present Standby output is on output is disabled Power supply failure includes overvoltage and overtemperature Green AC is present and main 12 V output is enabled Uplink module bay identification Moonshot 6SFP Uplink Module components ...

Страница 14: ...h supported HP transceiver modules that are compatible with the data center port type Moonshot 6SFP Uplink Module LEDs and buttons Item Description Status 1 Uplink module UID LED button Solid blue Switch module ID is selected Flashing blue Switch module firmware update is in progress Off Switch module ID is not selected 2 Uplink module health LED Green Normal operation Flashing amber Degraded cond...

Страница 15: ...t Ethernet traffic only QSFP ports support the following pluggable Ethernet transceiver modules HP 40GBASE QSFP HP 40GBASE QSFP SR4 HP 40GBASE QSFP DAC HP 40GBASE QSFP to 4x10G SFP Any available port can be used to connect to the data center Ensure the port is populated with supported HP transceiver modules that are compatible with the data center port type Moonshot 4QSFP Uplink Module LEDs and bu...

Страница 16: ...ition Off No power 3 Uplink module link LED Solid green Link Off No link 4 Uplink module activity LED Flashing green Activity Off No activity 5 Reset button Resets the switch module HP Moonshot 1500 Chassis Management module components Item Description Label 1 iLO CM management port iLO MGMT 2 iLO CM link port disabled by default LINK 3 Moonshot 1500 CM module HP APM port RCM 4 Moonshot 1500 CM mo...

Страница 17: ... port link LED iLO MGMT 2 iLO CM management port activity LED iLO MGMT 3 iLO CM link port link LED LINK 4 iLO CM link port activity LED LINK 5 Moonshot 1500 CM module UID LED button 6 Moonshot 1500 CM module health LED Chassis internal components Up to 45 cartridges and two switch modules can be installed in the HP Moonshot 1500 Chassis ...

Страница 18: ...Identifying components and LEDs 18 Cartridge slot and switch module bay identification The chassis provides 45 cartridge slots 1 45 and two switch module bays A B ...

Страница 19: ...l condition Off No power 3 Drive LED Green Activity Off No activity 4 Cartridge UID LED button Blue Cartridge ID is selected Flashing blue Cartridge firmware update is in progress Off Cartridge ID is not selected 5 Cartridge link LED button Flashing white Cartridges are linked Off Cartridge is not linked to other cartridges Depending on the cartridge installed there might be 0 1 or 2 drive LEDs Th...

Страница 20: ...Off No power 3 Switch module uplink activity LED Green Link Flashing green Activity Off No activity 4 Switch module downlink activity LED Green Link Flashing green Activity Off No activity 5 Switch module UID LED button Solid blue Switch module ID is selected Flashing blue Switch module firmware update is in progress Off Switch module ID is not selected 6 Access panel sensor Detects the presence o...

Страница 21: ...rmining the chassis rack spacing Up to seven chassis can be installed in a 36U 1200 mm 47 24 in deep rack If installing more than one chassis install the first chassis in the bottom of the rack and then install additional chassis by moving up the rack with each subsequent chassis Due to the height of the Moonshot 1500 Chassis chassis installation requires either the use of a rack rail adapter kit ...

Страница 22: ... or equipment damage be sure that the rack is adequately stabilized before installing the chassis CAUTION Always plan the rack installation so that the heaviest item is on the bottom of the rack Install the heaviest item first and continue to populate the rack from the bottom to the top CAUTION Be sure to keep the product parallel to the floor when installing the chassis Tilting the product up or ...

Страница 23: ...ct or at least four people to lift and stabilize the product pieces during assembly installation or removal especially when the chassis is not installed in the rack An additional person may be required to help align the chassis if the chassis is installed higher than chest level Observe local occupational health and safety requirements and guidelines for manual material handling HP recommends remo...

Страница 24: ...hold the Push tab on each rail until the chassis begins to slide into the rack Then release the Push tabs and continue to slide the chassis into the rack Press and hold the Push tab on each rail again when the rails lock at a 76 2 cm 30 inch extension Then release the Push tabs again and finish sliding the chassis into the rack Failure to release the Push tabs may cause damage to the rails ...

Страница 25: ...installed on the rack always install the blanking panel to ensure proper airflow The blanking panel is not needed when the rack rail adapter kit is installed To install the component 1 For round hole racks remove the guide pins and replace them with the guide pins included for round hole racks ...

Страница 26: ...ssis installation or additional components were ordered install each device using the procedures in this section If you perform any of the procedures in this section after powering on the chassis ensure proper airflow by ensuring that each bay inside the chassis and at the rear of the chassis is populated with either a component or a blank For component specific replacement information see the HP ...

Страница 27: ...tric shock or damage to the equipment Do not disable the power cord grounding plug The grounding plug is an important safety feature Plug the power cord into a grounded earthed electrical outlet that is easily accessible at all times Unplug the power cord from the power supply to disconnect power to the equipment Do not route the power cord where it can be walked on or pinched by items placed agai...

Страница 28: ...stalling the chassis 28 To install the component Install the power supply into the device bay and then press firmly until the power supply is seated Installing the fans Install the component as indicated ...

Страница 29: ... cartridge into the chassis Installing network components Switch information and guidelines on page 29 Removing the uplink module blank on page 32 Installing the uplink module on page 32 Installing the switch module on page 33 Switch information and guidelines Before installing the components review the following guidelines ...

Страница 30: ... the chassis Removing any component from bay A or bay B does not disrupt traffic for the other switch assembly For the most current product information see the release notes in the HP Moonshot Information Library http www hp com go moonshot docs Always use the HP recommended firmware version For more information on HP recommended firmware versions see the HP Moonshot Component Pack download websit...

Страница 31: ...s 31 Production network mapping The first network interface discovered by the operating system routes traffic through switch A The second network interface discovered by the operating system routes traffic through switch B ...

Страница 32: ...c from the service port management interface is routed through the iLO CM management port Removing the uplink module blank Remove the component as indicated Installing the uplink module CAUTION To avoid connectivity loss do not remove switches already in operation ...

Страница 33: ...lready installed verify the uplink module powers on and the uplink module health LED is green o If the switch module is not installed install the switch module before verifying LEDs For more information see Switch information and guidelines on page 29 5 After both components have been installed verify the switch firmware is at the HP recommended firmware version For more information see the HP Moo...

Страница 34: ...Installing the chassis 34 To install the component 1 Locate the switch module slot and then remove the blank 2 Prepare the switch module for installation ...

Страница 35: ...module is not installed install the uplink module before verifying LEDs For more information see Switch information and guidelines on page 29 5 Install the access panel and then return the chassis to the rack 6 After both components have been installed verify the switch firmware is at the HP recommended firmware version For more information see the HP Moonshot Component Pack download website http ...

Страница 36: ... network on page 36 2 Connect power cables to the chassis Connecting power cables and applying power to the chassis on page 38 3 Route cables on the cable management arm Routing cables on the cable management arm on page 38 Connecting the Moonshot System to a network Connect the Moonshot System to the following networks Data center management network on page 36 Data center production network on pa...

Страница 37: ...ment port The iLO CM management port is located on the Moonshot 1500 CM module on the rear of the chassis Data center production network To connect the chassis to a production network connect to any available SFP or QSFP port The SFP QSFP ports are located on the uplink module installed in the rear of the chassis Moonshot 6SFP Uplink Module ...

Страница 38: ...ying power to the chassis 1 Fans begin operating 2 iLO starts 3 Front panel LEDs display the status of initializing components o Switches begin initializing o Cartridges begin initializing 4 iLO runs fan and power tests Routing cables on the cable management arm Route all rear panel cables through the cable management arm For more information about the cable management arm see the Quick Deploy Rai...

Страница 39: ... Moonshot System components on page 40 For detailed configuration information see the following documents in the HP Moonshot Information Library http www hp com go moonshot docs o HP Moonshot iLO Chassis Management CLI User Guide o HP Moonshot System Configuration and Compatibility Guide Connect and configure a terminal for chassis configuration To connect and configure a terminal to communicate w...

Страница 40: ...s for each cartridge 1 Log in to the iLO CM firmware 2 Obtain MAC addresses show node macaddr all Configure the iLO CM firmware administrator account password Log in to the iLO CM firmware and change the administrator account password set user password user name new password Example set user password Administrator changed_password For more information about password configuration and restrictions ...

Страница 41: ...irmware version from the HP Moonshot Component Pack download site http www hp com go moonshot download 3 After downloading the firmware image upload all files to the iLO CM firmware repository add firmware file source URL 4 Verify the images were uploaded successfully show firmware files 5 Update the iLO CM firmware or system firmware update firmware filename 6 Update the cartridge firmware o Sing...

Страница 42: ...LI interface locally 2 Enter privileged exec mode At the switch prompt enter enable 3 Show the switch management IP address At the privileged exec prompt enter show serviceport If DHCP services are not available configure the serviceport IP address Be sure to configure the enable password before managing the switch remotely To configure the switch see the Switch Administrator s Guide and the Switc...

Страница 43: ...the associated switch The switch boots from the alternate flash file system The image is loaded and runs in the primary flash file system 10 Verify the firmware update was successful show bootvar 11 Update the boot loader on the switch update bootcode 12 Update the CPLDs on the switch NOTICE The CPLD update halts network traffic on the associated switch Once initiated do not interrupt the CPLD upd...

Страница 44: ... The type and number of power supplies depends on the cartridges installed in the chassis The following power capping modes are standard and are configurable in the power management controller Mode 0 No Redundancy All power capping is disabled This mode may be used to minimize any possible performance impact of power capping logic Mode 1 Max Performance with Redundancy This is the default power ca...

Страница 45: ...e 170 Watts Power Capacity 1818 Watts Status OK Powercap Mode Max Performance with Redundancy 3 Enter the following command to set the power capacity mode for the chassis set chassis powercap mode 0 1 2 Example hpiLO set chassis powercap mode 2 Set powercap mode to Full AC DC Redundancy Mode ...

Страница 46: ...ng Guide provides procedures for resolving common problems and comprehensive courses of action for fault isolation and identification issue resolution and software maintenance on the HP Moonshot System The document is available in the HP Moonshot Information Library http www hp com go moonshot docs ...

Страница 47: ... HP website http www hp com support Safety Compliance EnterpriseProducts Belarus Kazakhstan Russia marking Manufacturer Hewlett Packard Company Address 3000 Hanover Street Palo Alto California 94304 U S Local representative information Russian HP Russia HP Belarus HP Kazakhstan Local representative information Kazakh Manufacturing date The manufacturing date is defined by the serial number HP seri...

Страница 48: ...ng Products http www hp com support Networking Warranties Communications interference HP system compliance tests are conducted with HP supported peripheral devices and shielded cables such as those received with the system The system meets interference requirements of all countries in which it is sold These requirements provide reasonable protection against interference with radio and television c...

Страница 49: ...tic sensitive component or assembly Grounding methods to prevent electrostatic discharge Several methods are used for grounding Use one or more of the following methods when handling or installing electrostatic sensitive parts Use a wrist strap connected by a ground cord to a grounded workstation or computer chassis Wrist straps are flexible straps with a minimum of 1 megohm 10 percent resistance ...

Страница 50: ... level An altitude derating of 1 C per 304 8 m 1 8 F per 1000 ft to 3048 m 10 000 ft is applicable No direct sunlight allowed Upper operating limit is 3 048 m 10 000 ft or 70 kPa 10 1 psia Upper non operating limit is 9 144 m 30 000 ft Storage maximum humidity of 95 is based on a maximum temperature of 45 C 113 F Altitude maximum for storage corresponds to a pressure minimum of 70 kPa 10 1 psia Ch...

Страница 51: ...website http www8 hp com us en support drivers html If the problem cannot be resolved at the website call 1 800 633 3600 For more information about Care Packs see the HP website http pro aq sama houston hp com services cache 10950 0 0 225 121 html Customer Self Repair HP products are designed with many Customer Self Repair CSR parts to minimize repair time and allow for greater flexibility in perf...

Страница 52: ...e deux catégories de pièces CSR Obligatoire Pièces pour lesquelles la réparation par le client est obligatoire Si vous demandez à HP de remplacer ces pièces les coûts de déplacement et main d œuvre du service vous seront facturés Facultatif Pièces pour lesquelles la réparation par le client est facultative Ces pièces sont également conçues pour permettre au client d effectuer lui même la réparatio...

Страница 53: ... restituire dei componenti Qualora sia richiesta la resa ad HP del componente difettoso lo si deve spedire ad HP entro un determinato periodo di tempo generalmente cinque 5 giorni lavorativi Il componente difettoso deve essere restituito con la documentazione associata nell imballo di spedizione fornito La mancata restituzione del componente può comportare la fatturazione del ricambio da parte di ...

Страница 54: ...sifican en dos categorías Obligatorio componentes para los que la reparación por parte del usuario es obligatoria Si solicita a HP que realice la sustitución de estos componentes tendrá que hacerse cargo de los gastos de desplazamiento y de mano de obra de dicho servicio Opcional componentes para los que la reparación por parte del usuario es opcional Estos componentes también están diseñados para...

Страница 55: ...d en de locatie worden CSR onderdelen verzonden voor levering op de eerstvolgende werkdag Levering op dezelfde dag of binnen vier uur kan tegen meerkosten worden aangeboden indien dit mogelijk is gezien de locatie Indien assistentie gewenst is belt u een HP Service Partner om via de telefoon technische ondersteuning te ontvangen HP vermeldt in de documentatie bij het vervangende CSR onderdeel of h...

Страница 56: ...horas pode ser feita mediante uma taxa adicional Se precisar de auxílio entre em contato com o Centro de suporte técnico da HP para que um técnico o ajude por telefone A HP especifica nos materiais fornecidos com a peça CSR de reposição se a peça com defeito deve ser devolvida à HP Nos casos em que isso for necessário é preciso enviar a peça com defeito à HP dentro do período determinado normalmen...

Страница 57: ...Support and other resources 57 ...

Страница 58: ...Support and other resources 58 ...

Страница 59: ...CP Dynamic Host Configuration Protocol HP APM HP Advanced Power Manager iLO Integrated Lights Out PDU power distribution unit QSFP enhanced quad small form factor pluggable SCP Secure Copy Protocol SFP small form factor pluggable SFP enhanced small form factor pluggable SFTP Secure File Transfer Protocol SSH Secure Shell ...

Страница 60: ...Acronyms and abbreviations 60 TFTP Trivial File Transfer Protocol UPS uninterruptible power system ...

Страница 61: ...oviding documentation that meets your needs To help us improve the documentation send any errors suggestions or comments to Documentation Feedback mailto docsfeedback hp com Include the document title and part number version number or the URL when submitting your feedback ...

Страница 62: ...nstall in rack 21 CLI accessing 42 compiling documentation 6 compliance 5 components 9 10 11 16 17 29 components identification 9 10 configuration 39 configuration of system 39 configuration chassis 39 configuration power 5 configuration switch 41 configure a terminal 39 configuring a power cap 44 configuring the chassis 39 connecting a serial cable to a laptop 39 connecting an Ethernet cable 36 c...

Страница 63: ...ts 29 installation rack rails 21 installation switch module 33 installation uplink module 32 installing a cartridge 29 installing the chassis 21 installing the rack rails 21 IP address viewing 40 42 J Japanese notice 5 L LED identification 9 LED cartridge health 19 LED drive health 19 LED health 10 19 20 LED link 19 LED UID 19 LEDs 10 19 20 LEDs front panel 10 19 LEDs power supply 13 LEDs troubles...

Страница 64: ... 50 setting the admin password 40 site requirements 5 space requirements 7 21 specifications 5 7 8 50 specifications chassis 50 specifications environmental 50 static electricity 49 support 51 support and other resources 51 switch firmware updating 43 switch guidelines 29 switch health LEDs 10 20 switch information 29 switch module 9 29 33 switch module bay numbering 18 switch module configuring 4...

Отзывы: