Troubleshooting 41
Troubleshooting
LED and audible alarm troubleshooting
Genera
l Alarm
LED
On
Batter
y LED
Batter
y Fault
LED
Site
Wiring
Fault
LED
Utility
LED
Overloa
d LED
Audible
alarm
Can
alarm be
silenced
("
Silencin
g an
audible
alarm
"
on page
31
)?
Condition
Off
Off
Off
Off
Green
Off
No audible
alarm
N/A
UPS is in Operate
mode (on page
27
)
Off
Off
Off
Off
Flashin
g
green
Off
No audible
alarm
N/A
UPS is in Standby
mode (on page
27
)
Off
Off
Off
Off
Red
Off
On—1 beep
every 5
seconds
Yes
UPS is in Auto-Bypass
mode (on page
28
)
Flashing
red
Off
Off
Off
Red
Off
On—1 beep
every 5
seconds
Yes
General alarm
condition—UPS is in
Auto-Bypass mode
("
General alarm
condition
" on page
42
)
Off
Off
Off
Off
Flashin
g red
Off
On—1 beep
every 5
seconds
Yes
Bypass is out of range
(on page
43
)
Off
Off
Flashin
g red
Off
Off
Off
On—1 beep
every 5
seconds
Yes
Battery test failure
("
Battery condition
"
on page
43
)
Off
Flashin
g red
Off
Off
Off
Off
On—1 beep
every 5
seconds
No
Low battery (no utility
power) ("
UPS is on
battery
" on page
43
)
Off
Off
Flashin
g red
Off
Off
Off
On—1 beep
every 5
seconds
Yes
Batteries are
disconnected ("
Battery
condition
" on page
43
)
Off
Red
Off
Off
Off
Off
On—1 beep
every 5
seconds
Yes
On battery—No utility
power ("
UPS is on
battery
" on page
43
)