background image

Page 6 

 

Installer’s Information Manual 

TERMINATION LOCATION AND CLEARANCES 

Vent pipe and combustion-air-supply pipe (when direct 
vented) may terminate through a roof or through a sidewall.  
Roof termination has the advantages of better pipe 
protection and fewer condensate -damage concerns .  Use 
the following guidelines when choosing a vent location:  

??

Flue gases can be corrosive.  When sidewall venting, 
protect walls with a corrosion resistant material.  Also, 
terminate away from plants and shrubs. 

??

Locate termination consistent with the National Fuel 
Gas Code, ANSI Z223.1/NFPA 54 or the CAN/CGA 
B149 Installation Codes. 

??

Locate termination away from other air intake or 
exhaust vents such as dryer vents, other gas appliance 
vents, or plumbing vents.   Allow at least 3 foot to any 
other vent.   

??

Terminal must not be located above a walkway, 
driveway or within 10 feet of an adjacent building. 

??

Do not locate termination underneath a veranda, 
porch, or deck. 

IN THE UNITED STATES: 

??

Allow a minimum clearance of 4 feet from electric 
meters, gas meters, regulators, and relief equipment. 

??

When non-direct venting, terminal must be at least 4 
feet below, or 4 feet horizontally from or one foot above 
any door, window or gravity air inlet into a building.  
Terminal must also be at least 3 feet above any forced-
air inlet located within 10 feet horizontally. 

??

When direct venting, vent terminal must be at least one 
foot from any opening through which flue gases could 
enter a building. 

IN CANADA: 

??

Allow 6 feet clearance to any mechanical air supply or 
service regulator vent and 6 feet horizontally to any gas 
meter, electric meter, or relief device. 

??

Do not terminate above a meter/regulator assembly 
within 3 feet horizontally of the vertical center line of 
the regulator 

??

Do not terminate within one foot (3 feet for 108,000 and 
126,000 Btu models) of a window or door that can be 
opened, a non-mechanical-air-supply inlet, or the 
combustion-air inlet of any other appliance 

EXISTING VENT CONSIDERATIONS 

When a Category I furnace is removed or replaced, the old 
venting system may not be properly sized to vent the 
remaining appliance(s), for example, a gas water heater.  
An improperly sized venting system may promote the 
formation of condensate, leakage or spillage. 

The following steps shall be followed with each appliance 
connected to the old venting system placed in operation, 
while any other appliances connected to the venting system 
are not in operation: 

1.  Seal any unused openings in the venting system ; 

2.  Inspect the venting system for proper size and 

horizontal pitch, as required in the National Fuel Gas 
Code, ANSI Z223.1/NFPA 54 or the CAN/CGA B149 
Installation Codes.  Determine that there is no 
blockage or restriction, leakage, corrosion and other 
deficiencies which could cause an unsafe condition; 

3.  In so far as is practical, close all building doors and 

windows and all doors between space in which 
appliance(s) connected to the venting system are 
located and other spaces of building. 

4.  Close fireplace dampers. 

5.  Turn on clothes dryers and any appliance not 

connected to the venting system.  Turn on any exhaust 
fans, such as range hoods and bathroom exhausts, so 
they shall operate at maximum speed.  Do not operate 
a summer exhaust fan. 

6.  Follow the lighting instructions.  Place the appliance 

being inspected in operation.  Adjust thermostat so 
appliance shall operate continuously;  

7.  Test for drafthood equipped appliance spillage at the 

drafthood relief opening after 5 minutes of main burner 
operation.  Use the flame of a match or candle; 

8.  After it has been determined that each appliance 

connected to the venting system properly vents when 
tested as outlined above, retu rn doors, windows, 
exhaust fans, fireplace dampers and any other gas -
burning appliance to their previous conditions of use; 

9.  If improper venting is observed during any of the above 

tests, the venting system must be corrected.  Follow 
the National Fuel Gas Code, ANSI Z223.1/NFPA 54 or 
CAN/CGA B149 Installation Codes to correct improper 
vent operation.  Any "common vent" re-sizing must 
approach minimum size determined using current 
venting tables. 

DIRECT OR NON-DIRECT VENTING? 

This furnace may be installed using either direct venting or 
non-direct venting.   

A direct-vented furnace takes all air for combustion directly 
into the furnace through a pipe from outdoors.  To direct 
vent this furnace you must install two pipes to the outdoors.  
One pipe supplies combustion air that the fu rnace needs to 
operate.  The other pipe vents flue gases to the outdoors. 

Use direct venting when indoor air may be contaminated 
with chemicals such as chlorine, fluorine, bromine or iodine.  
When these chemicals are burned with natural gas or 
propane gas, acids are produced that may decrease heat 
exchanger life.  You should also consider direct venting 
when furnace is installed in a space with limited combustion 
and ventilation air.  See “CONFINED SPACE 

Содержание 422690

Страница 1: ... give you the documents listed on opposite side You should immediately read the User s Information Manual for important safety information to keep y ou and your family safe Keep these as long as you keep your furnace Pass them on to future furnace purchasers or users If any of the documents are missing or illegible contact your installer or furnace manufacturer for replacement Throughout this manu...

Страница 2: ... in this manual Must is mandatory Should is advisory WARNING Read and follow the safety rules in this section and throughout this manual Failure to do so could cause improper furnace operation resulting in damage injury or death Rule 1 Use only gas approved for use in this furnace as indicated on furnace rating plate Use only natural gas in furnaces designed for natural gas Use only propane LP gas...

Страница 3: ...clearance for service WARNING Some insulating materials are combustible When a furnace is installed in an attic or other insulated space keep all insulating materials at least 12 inches away from furnace and combustion air inlet Failure to do so could cause a fire You may install furnace on non combustible flooring or on wood flooring WARNING Do not install furnace on carpeting tile or other combu...

Страница 4: ...0 2 0 2 OR 3 90 000 1 2 17 1 2 15 3 4 15 15 16 1 0 0 2 0 2 OR 3 90 000 3 4 20 1 2 18 3 4 18 15 16 1 0 0 2 0 2 OR 3 108 000 3 4 23 1 2 21 3 4 21 15 16 1 0 0 2 0 3 126 000 3 4 23 1 2 21 3 4 21 15 16 1 0 0 2 0 3 See Furnace Rating Plate located on blower door These are furnace dimensions See Sections 9 and 10 for proper ductwork and floor opening dimensions Certified for installation on wood flooring...

Страница 5: ...gs that may hold water Support horizontal portions of vent pipe every 5 feet 3 feet for SDR 21 or SDR 26 pipe Protect vent from freezing Long runs of vent pipe installed in an unconditioned space may require insulation to prevent freezing of condensate Furnace can be vented from either left or right side See Figure 2 As shipped furnace is setup for venting through the left side Right side venting ...

Страница 6: ...peration while any other appliances connected to the venting system are not in operation 1 Seal any unused openings in the venting system 2 Inspect the venting system for proper size and horizontal pitch as required in the National Fuel Gas Code ANSI Z223 1 NFPA 54 or the CAN CGA B149 Installation Codes Determine that there is no blockage or restriction leakage corrosion and other deficiencies whi...

Страница 7: ...126 000 Btu hr model may need a high altitude pressure switch when installed at elevations between 3000 and 4000 feet Above 4000 feet this model requires a high altitude switch for all installations All furnace models require the high altitude pressure switch when installed at elevations above 6000 feet The high altitude pressure switch is supplied with the LP Conversion Kit 4226000 and the Natura...

Страница 8: ...0 15 108 000 3 40 40 40 40 40 40 40 40 See Note 2 below 126 000 3 40 40 40 40 35 30 25 20 54 000 2 40 40 40 40 40 40 40 40 72 000 2 21 18 14 11 72 000 3 40 40 40 40 40 40 40 40 5001 6000 90 000 3 40 40 40 40 40 40 40 40 108 000 3 40 35 30 25 20 15 10 108 000 3 40 40 40 40 40 40 40 40 See Note 2 below 126 000 3 40 40 40 40 35 30 25 20 54 000 2 40 40 40 40 40 40 40 40 72 000 2 40 40 40 40 36 32 28 2...

Страница 9: ... Attach a combustion air pipe to combustion air inlet collar on top of furnace Use rubber coupling and hose clamps supplied with furnace See Figure 5 Figure 5 Combustion Air Pipe Connection to Furnace for Direct Vent NON DIRECT VENTING INSTRUCTIONS one pipe system DETERMINING VENT LENGTH See Table 2 for maximum vent pipe length Include any termination elbows when determining maximum allowable vent...

Страница 10: ... 60 55 50 108 000 3 85 80 75 70 65 60 55 50 See Note 2 126 000 3 62 57 52 47 42 37 32 27 54 000 2 43 40 37 33 30 27 24 20 72 000 2 21 18 14 11 72 000 3 150 150 150 150 150 150 150 150 5001 6000 90 000 3 70 65 60 55 50 45 40 35 108 000 3 85 80 75 70 65 60 55 50 See Note 2 126 000 3 62 57 52 47 42 37 32 27 54 000 2 110 106 104 100 96 92 88 84 72 000 2 50 46 43 40 36 32 29 25 72 000 3 150 150 150 150...

Страница 11: ...requirements of all gas appliances in the building You must also allow for reduction of air available for combustion and ventilation caused by exhaust fans range hoods and fireplaces Sufficient air must be provided to ensure there will not be a negative pressure in furnace room or space In addition there must be a positive seal between furnace and return air duct to avoid pulling air from burner a...

Страница 12: ...om an unconfined space within the building or from outdoors However if the building is of unusually tight construction all combustion air must come from outdoors Also if returnair is taken directly from a hallway or space next to furnace that communicates with furnace spaces all combustion air must come from outdoors WARNING You must provide permanent air openings to a confined furnace installatio...

Страница 13: ...0 108 000 27 6 113 000 126 000 31 5 7 153 000 144 000 36 7 153 000 When communicating with the outdoors through vertical ducts openings and ducts must have a minimum free area of one square inch per 4 000 Btu per hour of total combined input rating of all gas appliances within furnace space See Figure 11 and Table 3 Figure 11 All Air Through Vertical Ducts From Spaces That Freely Access The Outdoo...

Страница 14: ...piping is large enough for all appliances connected to it to operate at once without lowering gas supply pressure Failure to do so could cause lighting or burning problems on any of the appliances Always use a pipe thread compound that is resistant to propane LP gas solvent action Sparingly apply thread compound to all joints on male threads only starting two threads from the end INSTALLATION Gas ...

Страница 15: ...cal Code CSA C22 1 WARNING Failure to provide a proper electrical ground could result in electric shock or fire Provide furnace with its own separate electrical circuit and means of circuit protection Furnace must have an electrical disconnect switch located at furnace WARNING Failure to provide the above shut off means could result in electrical shock or fire Use electrical wiring that meets curr...

Страница 16: ...Page 16 Installer s Information Manual Figure 15 Furnace Wiring Diagram ...

Страница 17: ... is de energized Main blower remains energized for 60 seconds CONSTANT FAN MODE Thermostat calls for constant fan R and G terminals connected Fan Timer energizes main blower on heating speed A call for cooling mode while in constant fan mode causes main blower to change from heating to cooling speed Sixty seconds after the call for cooling mode ends main blower changes back to heating speed A call...

Страница 18: ...o bottom return air opening Bottom closure panel is available from manufacturer See Table 5 for bottom closure part numbers Table 5 Bottom Closure Part Numbers GAS INPUT Btu hr MOTOR HORSE POWER BOTTOM CLOSURE PART NUMBER 54 000 1 3 4045901 72 000 90 000 1 2 4045901 72 000 90 000 3 4 4045902 108 000 126 000 3 4 4045903 GAS INPUT and MOTOR HP can be found on furnace rating plate WARNING Failure to ...

Страница 19: ...25 X 1 72 000 90 000 108 000 126 000 3 4 20 X 25 X 1 20 X 25 X 1 GAS INPUT and MOTOR HP can be found on furnace rating plate FILTER CABINETS Use a bottom filter cabinet side filter cabinet or return air filter grille Field fabricated filter cabinets should allow 1 inch spacing between filter and furnace Placing a field supplied filter directly against furnace bottom or side will decrease airflow a...

Страница 20: ...lowly open equipment shut off valve in gas supply line just ahead of furnace 7 Slowly open 1 8 NPT manual shut off valve leading to manometer 8 Turn on all gas appliances attached to gas supply line 9 With furnace operating read gas supply pressure on manometer Natural gas supply pressure must be between 5 and 7 inches W C Propane gas LP supply pressure must be between 11 and 13 inches W C 10 If g...

Страница 21: ...place burner access panel using three screws removed in step 2 SECTION 14 CHECKING GAS INPUT RATE It is the installer s responsibility to see that the Btu input rate of the furnace is properly adjusted Under firing could cause inadequate heat primary heat exchanger corrosion and or ignition problems Over firing could cause sooting flame impingement and or overheating of heat exchanger WARNING Fail...

Страница 22: ...ustment 3 Start furnace following Operating Instructions on front door 4 Let furnace warm up for 6 minutes 5 Adjust manifold pressure to 10 0 inches W C 0 3 inches W C See Section 13 Manifold Pressure Adjustment WARNING Do not set Propane LP manifold pressure at 11 0 inches W C It could cause heat exchanger failure NOTE NOx reducing screens must be removed from each tube of California NOx furnaces...

Страница 23: ...al power and gas before changing orifices Follow this procedure 1 Turn off electricity at electrical disconnect switch next to furnace 2 Turn off equipment shut off valve in gas supply line just ahead of furnace 3 Remove three screws holding burner access panel in place Remove burner access panel 4 Starting with burner farthest from gas control remove main burner screws and main burners Note how b...

Страница 24: ...0 1 2 35 65 ML YEL 72 000 3 4 30 60 ML YEL 90 000 1 2 45 75 MH BLUE 90 000 3 4 35 65 MH BLUE 108 000 3 4 35 65 MH BLUE 126 000 3 4 45 75 MH BLUE Gas Input and Motor HP can be found on rating plate These are factory settings Table 10 Cooling Speed Selection GAS MOTOR AIR CONDITIONING TONNAGE INPUT SIZE AT 0 5 INCHES WC Btu hr HP 1 5 2 2 5 3 3 5 4 5 54 000 1 3 LO ML MH HI 72 000 1 2 LO ML HI 72 000 ...

Страница 25: ...should be set according to Table 9 Cooling speed should be set to meet cooling equipment requirements See Table 10 for cooling airflow capacities at 0 5 inch W C 6 Place one thermometer in supply air plenum approximately 2 feet from furnace Locate thermometer tip in center of plenum to ensure proper temperature measurement 7 Place second thermometer in return air duct approximately 2 feet from fur...

Страница 26: ...itches located near 24 volt terminal strip on Fan Timer 2 Determine switch settings for desired heating blower off delay See Figure 23 3 Set switches on Fan Timer using a small screwdriver NOTE Cooling blower off delay is fixed at 60 seconds and is not adjustable Figure 23 Heating Blower Off Delay SECTION 23 MAINTAINING FURNACE IN GOOD WORKING ORDER WARNING Use replacement parts listed in parts li...

Страница 27: ...Industries name Choose from the T87 round w subbase T834 heating and cooling or the T8699 Chronotherm III available in white only PROPANE CONVERSION KIT BELOW 6 000 ft Includes propane regulator spring kit propane pilot orifice and main burner orifices HIGH ALTITUDE PROPANE CONVERSION KIT ABOVE 6 000 ft Includes propane regulator spring kit propane pilot orifice main burner orifices and high altit...

Отзывы: