3 Installing the Rapid Freeze Flaker
4
Installation Conditions
Rapid Freeze Ice Flakers are designed to operate in ambient temperatures warmer than 50
°
F. Do
not install ice flaker(s) in refrigerated cold rooms or in areas where the ambient temperature is
lower than 50
°
F (10
°
C). If it is unavoidable, ice flakers may be installed in areas down to 45
°
F
(7
°
C) provided that three (3) electric rib heaters (available from the factory) are installed to heat the
bottom casting to prevent ice buildup on the three supporting ribs for the bottom bearing. If
installed in cold ambient conditions, it is advisable to supply the ice flaker with warmer water
through a water mixing valve, around 60
°
F (15
°
C).
When a combination of cold water and cold air temperature exists, the mixing valve and rib heaters
must be used.
Failure to do so will cause the lower water collecting trough and sump to plug
up with ice to the extent that the water may overflow into the ice storage bin in addition to
blocking the water inlet to the pump.
Also, it is advisable to direct air blowers and fans away
from the ice flaker as air velocity over the ice flaker will reduce the effectiveness of the heaters.
*** CAUTION ***
NEVER install an ice flaker in a cold room 45
°
F (7
°
C) or lower. The ice flaker warranty is void
if the ice flaker is installed in a cold room or outside where the ambient temperature may drop
below freezing.
*** CAUTION ***
Optimum surrounding air temperature range............60
°
F (15
°
C) to 95
°
F (35
°
C)
Minimum air temperature (without heater)...........................................50
°
F (10
°
C)
Minimum air temperature (with heater)................................................45
°
F (7
°
C)
Maximum air temperature....................................................................100
°
F (38
°
C)
Optimum water temperature range.............................60
°
F (15
°
C) to 80
°
F (25
°
C)
Minimum water temperature (without water mixing valve)..................45
°
F (7
°
C)
Minimum water temperature (water mixing valve must be used)........36
°
F (2
°
C)
Maximum water temperature..................................................................90
°
F (32
°
C)
Installation without ice bin
Rapid Freeze Ice Flakers may be installed under certain conditions without a typical ice bin.
When the flaker is installed without a bin, it must have a drainable condensate pan located under
the machine. The flaker must also be mounted high enough off the floor so there is no chance that
somebody may reach into the evaporator from below either with a pole, or their arm, while the
flaker is operating.
Refrigerating the ice storage bin is not normally necessary nor is it recommended. However, in
those cases where ice is to be discharged into an existing freezer room then, as a minimum, electric
heaters should be installed on the bottom casting and the sump regardless of the actual ambient
temperature of the air surrounding the ice flaker. Air from the freezer room should be directed
away from the ice flaker opening otherwise, the effectiveness of the heaters will be reduced. If the
storage area is held at 28
°
F (-8
°
C) or colder, it is advisable to install the ice flaker 1 to 2 feet above
the freezer and use a duct section to direct the ice into the storage bin.
Содержание Rapid Freeze
Страница 6: ......
Страница 16: ...6 SEAWATER MODEL INSTALLATION 10 ASSEMBLY DRAWING 11ESS 21ESS...
Страница 17: ...6 SEAWATER MODEL INSTALLATION 11 ASSEMBLY DRAWING 31ES 31ESS...
Страница 18: ...6 SEAWATER MODEL INSTALLATION 12 ASSEMBLY DRAWING 51ES 51ESS...
Страница 19: ...6 SEAWATER MODEL INSTALLATION 13 ASSEMBLY DRAWING 11EFS 21EFS...
Страница 20: ...6 SEAWATER MODEL INSTALLATION 14 ASSEMBLY DRAWING 51EFS...
Страница 21: ...6 SEAWATER MODEL INSTALLATION 15 ASSEMBLY DRAWING 10ESS 20ESS...
Страница 22: ...6 SEAWATER MODEL INSTALLATION 16 ASSEMBLY DRAWING 30ES 30ESS...
Страница 23: ...6 SEAWATER MODEL INSTALLATION 17 ASSEMBLY DRAWING 50ES 50ESS...
Страница 28: ...9 How The Rapid Freeze Flaker Operates 22 ICE FLAKER CUTAWAY DRAWING EXHIBIT 26...
Страница 38: ...12 Control Panel Wiring Diagrams 32 Control Panel Schematic E20T40 RL...
Страница 39: ...12 Control Panel Wiring Diagrams 33 460 3 60 WIRING E20T47...
Страница 40: ...12 Control Panel Wiring Diagrams 34 460 3 60 Control Panel Schematic E50U8 RL Large Capacity Single Circuit...
Страница 41: ...12 Control Panel Wiring Diagrams 35 460 3 60 Control Panel Schematic E50U9 RL Large Capacity Dual Circuit...
Страница 42: ...12 Control Panel Wiring Diagrams 36 220 1 50 Control Panel Schematic E20T40 RL 50...
Страница 43: ...12 Control Panel Wiring Diagrams 37 380 3 50 Control Panel Schematic E20T60...
Страница 44: ...12 Control Panel Wiring Diagrams 38 380 3 50 Control Panel Schematic E50U14 RL Large Capacity Single Circuit...
Страница 64: ...15 Service Adjustment 58 EXHIBIT 40...
Страница 75: ...SELECTIVE PURPOSE Manual Page 69...