Overview of settings
RETURN CONTR
Par.
Designation
Factory
10
20
30
40
50
Lev.
1
Minimum limit return temperature / reference value return
temperature
38 °C
HF
2
Switch-off difference
2 K
HF
3
Pump follow-on time
1 min
HF
SOLAR
Par.
Designation
Factory
10
20
30
40
50
Lev.
1
Switch-on difference
10 K
HF
2
Switch-off difference
5 K
HF
3
Minimum running time SOP
3 min
HF
4
Solar collector maximum temperature
100 °C
HF
5
Solar tank maximum limit (KSPF)
65 °C
HF
6
Solar mode of operation
2
HF
7
Heat generator cycle lock (only when parameter 06=1,3,4)
0,5 h
HF
8
Solar priority parallel changeover
10 K
HF
9
Solar heat balance
OFF
HF
SOLAR
RESET
Reset heat balance
HF
11
Volumetric fl ow rate
0,0 l/ min
HF
0,0 l/ IMP
12
Density, medium
1,05 kg/ l
HF
13
Specifi c thermal capacity, medium
3,6 KJ/ kgK
HF
14
Final switching-off temperature
120 °C
HF
15
Test cycle solar charging switch-over
10 min
HF
16
Switch-over temperature (SLVF)
60 °C
HF
17
Solar minimum temperature
OFF
HF
SOLID FUEL
Par.
Designation
Factory
10
20
30
40
50
Lev.
1
Minimum temperature
60 °C
HF
2
Maximum temperature
95 °C
HF
3
Switch-on difference
10 K
HF
4
Switch-off difference
5 K
HF
5
Clock block, heat generator
15
HF
MAIN SUPPLY
Par.
Designation
Factory
10
Lev.
1
PI-amplifi cation factor, P-portion Xp
0 %/ K
HF
2
PI-scanning time Ta
20 s
HF
3
PI -reset time Tn
600 s/ °C
HF
CASCADE
Par.
Designation
Factory
10
Lev.
1
Switch-off difference
3 K
OEM
2
Connecting delay
20
OEM
3
Switch-off delay
5
OEM
4
Switching output stage sequence
65
OEM
5
Stage reversal
OFF
OEM
6
Control stage
1
BE
7
Peak load stage
OFF
OEM
8
Group switch-over
OFF
OEM
9
DHW fast activation
OFF
OEM
10
Peak load elevation
10 K
OEM
BUS
Par.
Designation
Factory
10
20
30
40
50
Lev.
1
Bus address central device
10
HF
2
Bus right RS direct circuit
1
HF
3
Bus right RS mixer circuit 1
1
HF
4
Bus right RS mixer circuit 2
1
HF
BUFFER
Par.
Designation
Factory
10
20
30
40
50
Lev.
1
Minimum temperature
5/ 20 °C
HF
2
Maximum temperature
95 °C
HF
3
Temperature elevation, H-GEN
8/ 10/ 12K
HF
4
Switching difference
2/ 5/ 10K
HF
5
Forced discharge
OFF
HF
6
Skimming function switch-on difference
10 K
HF
7
Skimming function switch-off difference
5 K
HF
8
Start-up protection
OFF
HF
9
Discharge protection
OFF
HF
10
Buffer mode of operation
2/ 3
HF
11
Pump follow-on time
3 min
HF
12
Switch-off reference value temp.
70 °C
HF
13
H-GEN release temp. skimming function
60 °C
HF