Commissioning
Parameter 16 „Screed function“
(Parameter HC, MC1 or MC2)
Example:
Maximum fl ow temperature 40°C
1 Function heating
• On the starting day and on the 1st day constantly at 25°C, on each further day the demand value rises by 5°C until the maximum
fl ow temperature is reached. Subsequently the temperature is lowered again in the same gradations until the low point of 25°C
is reached.
Example: Set fl ow maximum temp.: 40°C
Starting day + 1st day: 25°C 5th - 15th day: constant heating with the max. fl ow temperature
2nd day: 30°C 16th day: 35°C
3rd day: 35°C 17th day: 30°C
4th day: 40°C 18th day: 25°C
2 Surface-ready heating
Starting day + 18 days
• Combination of 1 function heating and subsequently 2 surface-ready heating
3 Function heating and surface-ready heating
Starting day + 25 days
START 1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 t [TAGE]
55
45
35
25
Funktionsheizen
und
Belegreifheizen
START 1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 [TAGE]
55
45
35
25
3=Funktionsheizen und Belegreifheizen
T [°C]
VLSol
3 = Function heating and surface-ready heating
START
DAYS
• On the starting day and for the three following days at 25°C constantly
• Subsequently for 4 days at the set fl ow maximum temp., but limited to a maximum of 55°C
Starting day + 7 days
START 1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 t [TAGE]
55
45
35
25
Funktionsheizen
START 1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 TAGE]
55
45
35
25
1=Funktionsheizen
maximal 55°C einstellbar!
T [°C]
VLSol
1 = Function heating
START
DAYS
START 1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 t [TAGE]
55
45
35
25
Belegreifheizen
START 1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 [TAGE]
55
45
35
25
2=Belegreifheizen
T [°C]
VLSol
2 = Surface-ready heating
DAYS
START
55°C maximum set level!