4  Technical data

4.1  Application limits

Maximum operating pressure

1600

kPa

Maximum heating medium temperature

90

°C

Maximum supply air temperature

60

°C

Maximum extract air temperature

50

°C

The units cannot be used in:

 

Areas where there is danger of explosion

 

Places with a corrosive or aggressive environment

 

Damp locations

 

Spaces with a large amount of dust

Table 4:  Application limits

4.2  Flow rate, product parameters

Type

TV-2

TV-4

TV-5

Nominal air flow rate

m³/h

2100

4850

5700

Power consumption

kW

0.10

0.25

0.37

Current consumption

A

0.51

1.30

1.70

Supply voltage

V AC

230

230

230

Frequency

Hz

50

50

50

Max. mounting height

m

5.5

5.5

5.5

Max. horizontal reach

m

14.0

22.0

25.0

Table 5:  Technical data

4.3  Heat output

Temperature of the 

heating medium

80/60 °C

60/40 °C

Type

t

room

Q

t

S

∆p

W

m

W

Q

t

S

∆p

W

m

W

°C

kW

°C

kPa

l/h

kW

°C

kPa

l/h

TV-2

15

13.9

34.8

6.7

610

8.3

26.6

3.2

360

20

12.6

37.9

5.6

560

6.8

29.7

2.3

300

TV-4

15

33.5

35.6

11.5

1480

19.4

26.9

4.8

850

20

30.3

38.6

9.5

1340

15.9

29.8

3.5

700

TV-5

15

50.2

41.3

15.7

2220

29.2

30.3

6.5

1280

20

45.4

43.8

13.0

2000

23.9

32.5

4.7

980

Legend:

t

room

  =  Room air temperature

=  Heat output

t

S

 

 =  Supply air temperature

∆p

W

  =  Water pressure drop

m

W

=  Water quantity

Table 6:  Heat output

8

TopVent

®

 TV

Design, installation and operation

Technical data

4 216 284-en-05

Содержание TopVent TV Series

Страница 1: ...TopVent TV Design installation and operation TopVent TV Recirculation unit for heating spaces up to 6 m in height...

Страница 2: ...nd data 9 4 5 Dimensions and weights 9 4 6 Specification text 9 5 Transport and installation 10 5 1 Delivery 10 5 2 Requirements for the installation site 10 5 3 Installation 11 5 4 Hydraulic installa...

Страница 3: ...and above this use is considered to be not as intended The manufacturer can accept no liability for damage resulting from improper use 1 2 User group The units are only allowed to be installed operate...

Страница 4: ...read the operating instructions before unpacking installing commis sioning and before maintaining the equipment Store the operating instructions so that they are easily accessible Observe any attached...

Страница 5: ...sts of the following components Heat exchanger consisting of copper tubes and aluminium fins Axial fan with energy saving EC motor and flow optimised fan blades infinitely variable maintenance free an...

Страница 6: ...tact switch The connected units are switched on via door contact if the door is open digital input Adjusting the fan speed The required speed can be infinitely adjusted Pump or valve control The EasyT...

Страница 7: ...its switch on Upon reaching the setpoint value the units switch off again Adjusting the fan speed The required speed can be infinitely adjusted Fig 3 EasyTronic TV room temperature controller EasyTron...

Страница 8: ...1 70 Supply voltage VAC 230 230 230 Frequency Hz 50 50 50 Max mounting height m 5 5 5 5 5 5 Max horizontal reach m 14 0 22 0 25 0 Table 5 Technical data 4 3 Heat output Temperature of the heating med...

Страница 9: ...TV Recirculation unit for heating spaces up to 6 m in height Sturdy casing made of ABS with pigment additive for UV protection front in RAL 9016 Traffic white and back in RAL 7037 Dusty grey heat exch...

Страница 10: ...veries and possible transport damage immediately in writing 5 2 Requirements for the installation site Position the units according to the system layout Comply with the minimum and maximum distances A...

Страница 11: ...opening Position the retaining bracket 3 over the openings Insert M10 screws 4 into the bushes Turn the retaining bracket to the desired position in relation to the unit Tighten the screws to secure t...

Страница 12: ...the air distribution Insulate the hydraulic lines Hydraulically balance the pipework for the the individual units within a control zone to ensure even distribution Attention Danger of damaging the un...

Страница 13: ...d connection boxes Install the connection box close to the unit distance 0 5 m Options for EasyTronic EC Wire the external room temperature sensor to the EasyTronic EC Wire the door contact to the Eas...

Страница 14: ...E 2x1 5 mm 2 1 2x1 0 mm 13 44 L PE L N PE AIN GND N 1 2 3G1 5 mm min 1 2 GNYE 2x1 0 mm 1 2 PE N L 1 2 PE N L 1 2 1 2 L N PE Connection box by the installer TopVent TV Door contact Pump or valve Extern...

Страница 15: ...x1 0 mm 1 2 N 1 2 PE L N 2x1 5 mm N L PE L N PE AIN GND N 1 2 3G1 5 mm min 1 2 GNYE 2x1 0 mm 1 2 PE N L 1 2 PE N L 1 2 1 2 L N PE EasyTronic TV Connection box by the installer TopVent TV further TopVe...

Страница 16: ...e casing base e g using a screw driver Break through the casing base along the perforation Insert the cables through this opening Connect the cables to the connectors Screw the base onto a flush mount...

Страница 17: ...ced Are all the control components installed and wired Are all of the respective trade groups installer electrician etc present at the scheduled time Are the system operating personnel present for tra...

Страница 18: ...en working on electrical systems When working in the unit take precautions against unprotected sharp metal edges Immediately replace damaged or removed informational and warning signs Following mainte...

Страница 19: ...of fatal injury from directly touching live parts even after the unit is switched off Only open the unit after waiting 5 minutes Drain the heating medium circuit Dismantle all media connections Disco...

Страница 20: ...90 Vaduz Liechtenstein Tel 423 399 24 00 info klimatechnik hoval com www hoval com United Kingdom Hoval Ltd Northgate Newark Notts NG24 1JN Tel 01636 672711 hoval hoval co uk www hoval co uk 20 421628...

Отзывы: