6 Technical data
6.1 Application limits
Extract air temperature
max.
°C
50
Supply air temperature
max.
°C
60
Temperature of the heating medium
1)
max.
°C
90
Pressure of the heating medium
max.
kPa
800
Air flow rate
Size 6:
Size 9:
min.
min.
m³/h
m³/h
3100
5000
Condensate quantity
Size 6:
Size 9:
max.
max.
kg/h
kg/h
90
150
The units cannot be used in:
■
Damp locations
■
Places with a corrosive or aggressive environment
■
Spaces with a large amount of dust
■
Areas where there is danger of explosion
1)
Design for higher temperatures on request
Table 4: Application limits
6.2 Electrical connection
Unit type
TH-6
MH-6
TH-9
MH-9
TC, THC,
MC, MHC
Supply voltage
V AC
3 × 400
3 × 400
3 × 400
Permitted voltage tolerance
%
± 5
± 5
± 5
Frequency
Hz
50
50
50
Connected load
kW
1.5
2.1
3.6
Current consumption max.
A
2.9
4.0
5.9
Series fuse
A
13
13
13
Protection rating
-
IP 54
IP 54
IP 54
Table 5: Electrical connection
6.3
Air flow rate
Unit size
6
9
Nominal air flow rate
m³/h
6000
9000
Floor area covered
m²
537
946
Table 6:
Air flow rate
12
TopVent
®
TH | TC | THC | MH | MC | MHC
Operating instructions
Technical data
4 218 828-en-01
4 218 828-en-01