4 214 174 V00 KDT GLT-Modul TTE_EN.docx
17 / 26
11. Reference value detection
Reference values for heating, cooling and hot water are registered and each one signalled on an output.
The reference values of the consumers are registered for the functions of heating, cooling and hot water, and are
displayed on the allocated output. If the reference value is > 0, the correspondingly allocated output is switched
on after the set triggering delay has expired. If the nominal value = 0 or if no reference value is received, the
output is switched off.
Any reference values generated in the module must also be taken into account.
If no output is allocated, the function has no effect.
Note:
The reference value ID acts on consumer reference values (heating, cooling, hot water)!
11.1. Reference value detection menu
Parameter Designation
Value
Min. Max. Comment
R W
29-080
Set point detect.
output delay
heating
0.5 min
0.0
99.0 Set point detect. output delay heating
3 3
29-081
Stpt. detection
output delay
cooling
0.5 min
0.0
99.0 Set point detect. output delay cooling
3 3
29-082
DHW setpoint
detection output
delay
0.5 min
0.0
99.0 Set point detect. output delay hot water
3 3
32-049
Allocation
setpoint det.
output heating
0
0
14
Allocation setpoint det. output heating
3 3
32-050
Allocation
setpoint det.
output cooling
0
0
14
Allocation setpoint det. output cooling
3 3
32-051
Alloc. stpt.
detection hot
water output
0
0
14
Alloc. stpt. detection hot water output
3 3