7.2  Alarm processing

Precondition: The 

User

 operator level is active (password entry see section 2.6)

O

verview   i     01/01

ZONE       Mode SA2

REMU 01 02

RECU 61 62
10:18   !     28.07.17

Calling up the alarm list from any menu:

 

Shortly press the button  .

 

The alarm list appears.

Alarms           1/006

 Date  Time  Unit ID

-

28.07 10:00 0102 0208

-04.08 14:11 0102*0301

 

Navigate to the alarm with    .

 

Confirm with 

.

 

Navigate to the next alarm to be 

confirmed with 

  .

 

Confirm with 

, and so on.

Alarms           1/006

 Date  Time  Unit ID

-

88.07 10:00 0102!0208

 

The icon for the alarm status changes 

to '

!

'.

 

Rectify fault.

 

If required, contact Hoval customer 

service.

Alarms reset:

 

Press   key and hold it down for 

3 seconds.

 

Back to 

Overview

: Press  .

7.3  Alarm list

The following table contains an overview of all alarms and their cause. Contact 

Hoval customer service to have faults rectified.

ID Alarm

Cause

System reaction

Remedy

  1 Frost protection (supply air)

The supply air temperature has 

dropped below 13 °C.

The mixing valve heating opens contin-

uously. The (optional) heating pump 

switches on.

Check the heat supply and the 

unit hydraulics, rectify error.

Reset alarm.

The supply air temperature has 

dropped below 8 °C.

The frost protection alarm (supply air) is 

tripped.

The heating mixing valve opens 100%.

The unit switches off.

  2 Frost protection (water return)

The return temperature has dropped 

below 15 °C.

The mixing valve heating opens contin-

uously. The (optional) heating pump 

switches on.

The return temperature has dropped 

below 7 °C.

The frost protection alarm (water return) is 

tripped.

The heating mixing valve opens 100%.

The unit switches off.

  3 Fault supply air fan 1

The fan motor has a fault or the corre-

sponding circuit breaker has tripped.

The unit switches off.

Switch on automatic circuit 

breaker again.

  5 Main switch off

The main switch is set to '0'.

Set main switch to position '1'.

20

TopTronic

®

 C

System control for TopVent

®

Alarms

4 216 689-en-01

Содержание TopTronic C-SYS

Страница 1: ...System control for TopVent C SYS Operating Manual TopTronic C System control for TopVent C SYS 4216689 en 01...

Страница 2: ...Menu tree 9 4 Operating examples 11 4 1 Switching operating modes 11 4 2 Setting the room temperature setpoint 12 4 3 Programming the weekly calendar 13 5 Info menus 15 5 1 Info menu zone 15 5 2 Info...

Страница 3: ...the weekly calendar Display and handling of alarms Password protection Intended use also includes compliance with the operating instructions Any usage over and above this use is considered to be not a...

Страница 4: ...s occurred Key lights up An already acknowledged alarm is still present Open activated function fields Call up Main menu Save delete switching points Return to the overview Exit without saving Navigat...

Страница 5: ...operating modes AUTO Automatic mode CPR Cooling protection DES Destratification ES Forced off zone EXT External control by building management system NCS Night cooling OPR Overheat protection OPTC St...

Страница 6: ...active CPR Cooling protection If the room temperature drops below the set value for cooling protection the unit heats up the room in recirculation operation OPR Overheating protection If the room tem...

Страница 7: ...01 02 RECU 61 62 10 18 28 07 17 In Overview with the cursor on the O press the key Password 01 01 Please enter the password 00000 10 18 28 07 17 Enter the 1st digit of the password with factory setti...

Страница 8: ...u 4 5 Operating menu Weekly calendar Date Time Logout In Main menu navigate to Date Time with Confirm with Date Time change Date 28 07 17 Time 10 18 03 10 18 28 07 17 Navigate to the next day with Set...

Страница 9: ...01 Info menu 03 06 REMU 01 Info menu 02 06 REMU 01 Info menu 01 06 REMU 01 Info menu supply air unit No 01 Pages 01 06 Overview i 01 01 ZONE Mode SA2 REMU 01 02 RECU 61 62 10 18 28 07 17 Info menu 06...

Страница 10: ...ekly calendar Date Time Logout Weekly calendar 1 50 Weekly calendar Accessible in User level only Main menu 4 5 Overview Operating menu Weekly calendar Date Time Logout Date Time change Date Time Acce...

Страница 11: ...ar Date Time Logout In Main menu navigate to Operating menu with Confirm with Operating menu 01 05 ZONE REMU Operating mode 3 1 ST 2 SA1 3 SA2 4 REC1 5 REC 6 EXT 7 AUTO 10 18 28 07 17 In Operating men...

Страница 12: ...u with Confirm with Operating menu 01 05 ZONE REMU Operating mode 7 1 ST 2 SA1 3 SA2 4 REC1 5 REC 6 EXT 7 AUTO 10 18 28 07 17 Navigate to page 2 of the operating menu with Operating menu 02 05 ZONE Ro...

Страница 13: ...sor on the O press the key The Main menu appears Main menu 3 5 Overview Operating menu Weekly calendar Date Time Logout In Main menu navigate to Weekly calendar with Confirm with Weekly calendar 0 00...

Страница 14: ...g point with In the same way enter the switching points for Wednesday to Friday After completing the weekly calendar go back to Overview with Checking the weekly calendar Weekly calendar 10 10 IDX Day...

Страница 15: ...enabling heating cooling applies to automatic changeover Info menu 03 05 ZONE External setting Heating 10 18 28 07 17 Displays External setting heating cooling applies to manual changeover Info menu 0...

Страница 16: ...pump Off Off Supply air fan 0 10 18 28 07 17 Displays Heating pump switching command and feedback Cooling pump switching command and feedback Current air flow rate in of the nominal air flow rate Info...

Страница 17: ...mp Off Off Supply air fan 0 10 18 28 07 17 Displays Heating pump switching command and feedback Cooling pump switching command and feedback Current air flow rate in of the nominal air flow rate Info m...

Страница 18: ...U 10 18 28 07 17 Setting night cooling Enabling Room setpoint and Fan setpoint Navigate to the input field with Set value with Confirm with Operating menu 04 05 ZONE Runtime Button ST 30min Button REC...

Страница 19: ...es A new alarm has occurred Symbol lights up An already acknowledged alarm is still present 2 Alarm status of unit No 02 In the alarm list 1 2 3 4 Alarms 1 006 Date Time Unit ID 28 07 10 00 0102 0208...

Страница 20: ...stem reaction Remedy 1 Frost protection supply air The supply air temperature has dropped below 13 C The mixing valve heating opens contin uously The optional heating pump switches on Check the heat s...

Страница 21: ...The sensor or the cabling has an interruption 232 Fault return temperature sensor shortcut The sensor or the cabling has a short circuit The unit continues to operate with a return temperature of 99 C...

Страница 22: ...and actuator rectify the error Reset alarm 606 Feedback alarm actuator Air Injector The Air Injector is sticking or the actu ator is defective or a manual interven tion is in progress Check the mecha...

Страница 23: ...of temporary REC operation 1 9999 30 min Duration of temporary ST operation 1 9999 30 min Fan setpoint night cooling 50 100 100 Min limit discharge direction 0 100 0 Operating hours filter exchange 0...

Страница 24: ...490 Vaduz Liechtenstein Tel 423 399 24 00 info klimatechnik hoval com www hoval com United Kingdom Hoval Ltd Northgate Newark Notts NG24 1JN Tel 01636 672711 hoval hoval co uk www hoval co uk 24 TopTr...

Отзывы: