background image

ID Alarm

Cause

System reaction

Remedy

290 Fault cold generation

Fault cold supply

All units in the zone continue to run without 

cooling.

Rectify fault.

291 Fault condensate pump

The pump has a fault or the corre-

sponding circuit breaker has tripped.

The unit continues to run without cooling. Rectify fault.

300 Max limit room temperature

The room temperature has exceeded 

the maximum warning limit.

Reduce the room temperature 

below the warning limit or adjust 

the limit value.

301 Min limit room temperature

The room temperature has dropped 

below the minimum warning limit.

Increase the room temperature 

above the warning limit or adjust 

the limit value.

302 Max limit supply air temperature

The supply air temperature has 

exceeded the maximum warning limit.

Eliminate the reason why the 

supply air temperature was 

exceeded or adjust the limit value.

303 Min limit supply air temperature

The supply air temperature has 

dropped below the minimum warning 

limit.

Eliminate the reason why the 

supply air temperature was under-

shot or adjust the limit value.

325 Fault external setpoint extract air/recir-

culation damper 

The signal or the cabling has a fault.

327 Fault external operating mode signal 

mixed air units

The signal or the cabling has a fault.

328 Fault external operating mode signal 

recirculation units

The signal or the cabling has a fault.

600 Feedback alarm heating valve

The valve is sticking or the actuator is 

defective or a manual intervention is in 

progress.

Check the mechanical and elec-

trical systems of the valve and 

actuator, rectify the error.

Reset alarm.

601 Feedback alarm cooling valve

605 Feedback alarm recirculation damper

The damper is sticking or the actuator 

is defective or a manual intervention is 

in progress.

Check the mechanical and elec-

trical systems of the damper and 

actuator, rectify the error.

Reset alarm.

606 Feedback alarm actuator Air-Injector

The Air-Injector is sticking or the actu-

ator is defective or a manual interven-

tion is in progress.

Check the mechanical and elec-

trical systems of the Air-Injector 

and actuator, rectify the error.

Reset alarm.

607 Feedback alarm heating pump

The control for feedback has a fault or 

a manual intervention is in progress.

Rectify fault.

Reset alarm.

608 Feedback alarm cooling pump
613 Feedback alarm changeover valves 

heating

614 Feedback alarm changeover valves 

cooling

721 Local protection mode L_REC active

Protection mode was activated as the 

result of another alarm.

The unit continues to run in L_REC protec-

tion mode.

Rectify fault.

722 Central protection mode REC active

Protection mode was activated as the 

result of another alarm.

All units in the zone continue to run in 

protection mode REC.

Rectify fault.

723 Emergency operation active

An external signal has activated the 

emergency operation function.

The unit runs in emergency operation.

Deactivate the external signal.

900 Zone offline

There is no longer any communication 

with this zone.

All units in the zone run in offline mode. 

Online functions are not active.

Check IP network.

Rectify fault.

901 Unit offline

There is no longer any communication 

with this unit.

The unit runs in offline mode with prede-

fined parameters.

Online functions are not active.

The frost protection function is not ensured.

Check cabling.

Rectify fault.

902 Recirculation unit offline

903 Forced datapoint

There is manual intervention on a data 

point.

The system or the unit is working with the 

forced data point.

Call Hoval customer service.

907 Expansion offline

There is no longer any communication 

with this controller.

Not all functions are active.

Call Hoval customer service.

908 Fault universal I/O port 

There is a signal fault on a controller 

connection.

Not all functions are active.

Call Hoval customer service.

22

TopTronic

®

 C

System control for TopVent

®

Alarms

4 216 689-en-01

Содержание TopTronic C-SYS

Страница 1: ...System control for TopVent C SYS Operating Manual TopTronic C System control for TopVent C SYS 4216689 en 01...

Страница 2: ...Menu tree 9 4 Operating examples 11 4 1 Switching operating modes 11 4 2 Setting the room temperature setpoint 12 4 3 Programming the weekly calendar 13 5 Info menus 15 5 1 Info menu zone 15 5 2 Info...

Страница 3: ...the weekly calendar Display and handling of alarms Password protection Intended use also includes compliance with the operating instructions Any usage over and above this use is considered to be not a...

Страница 4: ...s occurred Key lights up An already acknowledged alarm is still present Open activated function fields Call up Main menu Save delete switching points Return to the overview Exit without saving Navigat...

Страница 5: ...operating modes AUTO Automatic mode CPR Cooling protection DES Destratification ES Forced off zone EXT External control by building management system NCS Night cooling OPR Overheat protection OPTC St...

Страница 6: ...active CPR Cooling protection If the room temperature drops below the set value for cooling protection the unit heats up the room in recirculation operation OPR Overheating protection If the room tem...

Страница 7: ...01 02 RECU 61 62 10 18 28 07 17 In Overview with the cursor on the O press the key Password 01 01 Please enter the password 00000 10 18 28 07 17 Enter the 1st digit of the password with factory setti...

Страница 8: ...u 4 5 Operating menu Weekly calendar Date Time Logout In Main menu navigate to Date Time with Confirm with Date Time change Date 28 07 17 Time 10 18 03 10 18 28 07 17 Navigate to the next day with Set...

Страница 9: ...01 Info menu 03 06 REMU 01 Info menu 02 06 REMU 01 Info menu 01 06 REMU 01 Info menu supply air unit No 01 Pages 01 06 Overview i 01 01 ZONE Mode SA2 REMU 01 02 RECU 61 62 10 18 28 07 17 Info menu 06...

Страница 10: ...ekly calendar Date Time Logout Weekly calendar 1 50 Weekly calendar Accessible in User level only Main menu 4 5 Overview Operating menu Weekly calendar Date Time Logout Date Time change Date Time Acce...

Страница 11: ...ar Date Time Logout In Main menu navigate to Operating menu with Confirm with Operating menu 01 05 ZONE REMU Operating mode 3 1 ST 2 SA1 3 SA2 4 REC1 5 REC 6 EXT 7 AUTO 10 18 28 07 17 In Operating men...

Страница 12: ...u with Confirm with Operating menu 01 05 ZONE REMU Operating mode 7 1 ST 2 SA1 3 SA2 4 REC1 5 REC 6 EXT 7 AUTO 10 18 28 07 17 Navigate to page 2 of the operating menu with Operating menu 02 05 ZONE Ro...

Страница 13: ...sor on the O press the key The Main menu appears Main menu 3 5 Overview Operating menu Weekly calendar Date Time Logout In Main menu navigate to Weekly calendar with Confirm with Weekly calendar 0 00...

Страница 14: ...g point with In the same way enter the switching points for Wednesday to Friday After completing the weekly calendar go back to Overview with Checking the weekly calendar Weekly calendar 10 10 IDX Day...

Страница 15: ...enabling heating cooling applies to automatic changeover Info menu 03 05 ZONE External setting Heating 10 18 28 07 17 Displays External setting heating cooling applies to manual changeover Info menu 0...

Страница 16: ...pump Off Off Supply air fan 0 10 18 28 07 17 Displays Heating pump switching command and feedback Cooling pump switching command and feedback Current air flow rate in of the nominal air flow rate Info...

Страница 17: ...mp Off Off Supply air fan 0 10 18 28 07 17 Displays Heating pump switching command and feedback Cooling pump switching command and feedback Current air flow rate in of the nominal air flow rate Info m...

Страница 18: ...U 10 18 28 07 17 Setting night cooling Enabling Room setpoint and Fan setpoint Navigate to the input field with Set value with Confirm with Operating menu 04 05 ZONE Runtime Button ST 30min Button REC...

Страница 19: ...es A new alarm has occurred Symbol lights up An already acknowledged alarm is still present 2 Alarm status of unit No 02 In the alarm list 1 2 3 4 Alarms 1 006 Date Time Unit ID 28 07 10 00 0102 0208...

Страница 20: ...stem reaction Remedy 1 Frost protection supply air The supply air temperature has dropped below 13 C The mixing valve heating opens contin uously The optional heating pump switches on Check the heat s...

Страница 21: ...The sensor or the cabling has an interruption 232 Fault return temperature sensor shortcut The sensor or the cabling has a short circuit The unit continues to operate with a return temperature of 99 C...

Страница 22: ...and actuator rectify the error Reset alarm 606 Feedback alarm actuator Air Injector The Air Injector is sticking or the actu ator is defective or a manual interven tion is in progress Check the mecha...

Страница 23: ...of temporary REC operation 1 9999 30 min Duration of temporary ST operation 1 9999 30 min Fan setpoint night cooling 50 100 100 Min limit discharge direction 0 100 0 Operating hours filter exchange 0...

Страница 24: ...490 Vaduz Liechtenstein Tel 423 399 24 00 info klimatechnik hoval com www hoval com United Kingdom Hoval Ltd Northgate Newark Notts NG24 1JN Tel 01636 672711 hoval hoval co uk www hoval co uk 24 TopTr...

Отзывы: