TECHNICAL INFORMATION
3.4
Short description of the automatic firing
unit BIC 335
The automatic firing unit operates both without controller
(TTE) and also without room station (RS-OT). The auto-
matic firing unit comprises the following functions
- PWM- fan (230V~)
- Modulating operation
- Inputs for
Flow sensor
Return sensor
Flue gas sensor
Gas pressure deflector
Air pressure deflector:
(not used)
Water pressure deflector
Safety temperature limiter:
(external flue gas thermostat)
HW-buffer sensor
Outdoor sensor
Locking entry:
(Burner blocking)
- Status exit „Failure“ (invertible by parameter setting)
- Three-way-valve control for heating/hot water or loa-
ding pump control (230V~exits); Exit for a three-way-
valve / HW loading pump is invertible by a parameter.
- Collective electrode for ignition and flame guide (Ioni-
sation)
- Main gas valve (ev. LPG- valve) / heating room
venti
-
lation accessable
- Interface to display
- OpenTherm- interface (RS-OT, TTE)
- RS 232- interface to PC
-
Start attempts: 4
-
Safety period: 5 sek
-
Ignition period: 5 sek
- Pre-ventilation period: 20 sek
- After-run time main pump / heating pump
(230V ~): 10 min
- After-run time three-way valve / HW-loading pump: 2 min
- Restart locking after a heat demand: 2 min
- Restart locking after a temperature blocking: 2 min
Fuses
On the automatic firing unit theres is a mains fuse. The
breakdown of this fuse (2AT) is noticeable by an empty
display even the main deflector is on.
Ionisation flow
The value of the ionisation flow is noted on the informati-
on level and appears as step 8. The access to the infor-
mation level is explained in 3.5.