34

Hoval STU Wood Pellet Boiler

With the KINDLE/IGNITION switch in this position and with a 

demand signal calling for operation of the Boiler and with the Flue 

Gas Temperature registering <50 °C, then the following sequence 

for Ignition occurs;

• Run Pellet Feed systems to prime or charge the retort

• This may take several minutes to complete and is site 

specific and pre programed on comissioning

• Hot Air Ignition Gun switches ON (A)

• ID Fan switches ON

• Wait for a set period (Approx 5 minutes)

• Hot Air Ignition Gun switches OFF

• Wait for a period (approx 10 minutes) to achieve the 

required Flue Gas temperature

• If the Flue Gas Temperature >50 °C then

• Switch ON FD fan

• Wait for a set period (approx 10 minutes)

• Stoker Pellet Feed system operates, initially on Low Fire, 

before normal modulation based on demand.

• If after priming the retort and running Igntion Gun/ID Fan 

the Flue Gas temperature remains <50 °C

• The Hot Air Ignition sequence (from (A)) is re initiated

• If after a further attempt (i.e. .the 3rd) to establish 

combustion, the Flue Gas Temperature remains <50 °C 

then the Stoker Control switches the stoker/boiler off.

If the Flue Gas Temperature is >50 °C when the demand signal is 

received the system will not fire the Ignition gun.
3. IMPORTANT. Once the fire has been established the operator 

should set KINDLE/IGNITION switch on the Stoker Control Panel 

to Kindle position.
4. If after the above the boiler has failed to light or combustion has 

not been established then the operator 

MUST NOT RESET

 the 

KINDLE/IGNITION switch to Ignition. 

Isolate the boiler 

electrically and report the fault to Hoval Service.
Standard Ignition (Manual)

From a 'Boiler Out' cold condition it is relatively easy to bring the 

boiler on-line within a few minutes by the introduction of an ignition 

source into a primed retort.
To set in operation:

• The operator should check that all the isolator switches 

associated with the motors on the stoker are in the ON 

position and that there is power to the Stoker Control 

Panel (ON/OFF to ON).

• On the Stoker control set the Wood Burner switch to 

AUTO, ID Fan Switch also set to AUTO.

• After a short delay (when both ID and FD fans operate) 

the pellet feed augers will begin to feed pellets into the 

retort.

• Run the Stoker until the retort fills with fuel - the pellets 

should be level or just below the last set of Turyres (or 

airways within the retort. It may be necessary to open the 

boiler door to check the level of fuel in the retort.

• Set Wood Burner Switch to OFF.

• Using the isolator switches on the motors, switch to OFF 

bothe PICK-UP and CONVEYOR (OR DELIVERY) augers.

• Open Boiler door.

• Add two small firelighters to the top of the retort and 

surround with some of the wood pellet fuel. Carefully ignite 

the firelighters.

• Close the Boiler Door

• Switch the Wood Burner switch to AUTO. This will 

operate the stoker without adding any further fuel into the 

retort and will also allow combustion to establish, as both 

the ID fan and then the FD fan start.

• After approx 10 minutes operation check the condition of 

the fire within the retort to ensure that combustion is fully 

established (using the sight glass on the front of the door 

of the boiler).

• IMPORTANT. Once the fire has established the isolating 

switches on both the PICK-UP and the CONVEYOR 

augers must be switched back to ON. This allows the 

resumption of fuel feed into the boiler.

• Leave Stoker operating in AUTO mode.

Ignition from 'Boiler Stand-By' or Kindle

In normal operation once ignition has taken place from cold (as 

described above) the boiler would normally be held in 'Stand-By' 

or kindle mode whenever there was no call for heat (e.g. overnight 

or over a weekend period).

Combustion of the wood pellet fuel is brought to a virtual standstill 

and a small permanent ignition source is held within the retort.

When the stoker control receives a demand signal to fire the pre 

purge process with both the FD and ID fans in operation 

re-initiates full combustion within a few minutes. The stoker control 

then responds to suit the load.

Note once ignition has been established the boilers can be held 

in Kindle (or stand-by mode) for up to 72 hours without the need 

to re-light the boilers. The boiler might run normally during a day, 

switch to kindle at the end of the day and kindle overnight (or over

a weekend). The following day(s) normal operation could resume 

without any need for manual intervention

If the boiler is kindled for an extended 72 hours period, then the 

BMS should be configured to operate the boiler for a short but 

continuous period (minimum 1 hour). Once this has occurred the 

boiler will resume kindle mode until next called by the BMS. 

The BMS should also be configured to operate system pump(s) 

during the above one hour period, followed by a suitable pump 

run-on period (max 30 minutes). When the stoker operates 

normally, a "Stoker Running" volt free signal is generated, which 

the BMS can use to start the system pump(s).

We recommend, however that the boiler is not routinely kindled 

for more than 72 hours. If this is the case, the boiler should be 

shut down as described below and re lit when required.

Always ensure there is sufficient wood pellet fuel covering the 

pick-up auger or available at the outlet of the pellet storage silo.

Boiler Shut Down

During Normal operation it is possible to temporarily interrupt the 

feeding of fuel into the boiler. This is necessary whenever the 

Boiler door is to be opened to access the combustion chamber. 

E.G. To check and inspect the fire or to remove any ash from 

around the retort within the Boiler.

With the boiler operating, to temporarily stop the boiler from firing 

fresh fuel;

• On the Stoker Control Panel, set the KINDLE/OFF/AUTO 

switch from AUTO to OFF. Set the ID FAN switch from 

AUTO to ID FAN ONLY.

• This halts the feeding of fuel into the boiler, and switches 

off the FD fan.

• The Boiler door can then be opened, by using the Tommy 

bar to loosen the nuts fastening the door shut. CAUTION 

the operator MUST stand behind the boiler door as the 

nuts are unloosened and the door is gradually opened. 

NEVER stand adjacent to the opening door.

Operating Instructions

Always ensure there is sufficient wood pellet fuel covering pick-up auger or available at the outlet of the pellet storage silo.

Содержание STU Series

Страница 1: ...Installation Operation and Maintenance Instructions STU wood pellet fired hot water boiler 150 1000kW STUman May 2010 WS2...

Страница 2: ...n Guidelines Entry to fuel Store 17 18 Typical Plantroom Layouts 19 21 Boiler Door Handing 22 Boilerhouse Ventilation Open Vented Pressurised Systems 23 Flues and Chimneys 24 Filling The System With W...

Страница 3: ...technical servicing or parts enquiries telephone fax or e mail Hoval quoting the boiler s serial number as above Tel 01636 593413 or 593435 Fax 01636 673532 e mail service hoval co uk or spares hoval...

Страница 4: ...n and use of this appliance Fuel Quality Requirement The design of the boiler stoker pellet handling system and store is dependant on using the correct quality wood pellet fuel The pellets should be f...

Страница 5: ...uel bed An optional ignition start system is available on request but this must be specified at the time of order The boiler comprises of a welded steel shell with a water jacket surrounding an oval c...

Страница 6: ...of flue gases ensures close combustion control as the air supply is adjusted to match the fuel feed The standard stoker design incorporates an airless kindle feature This allows the boiler under norm...

Страница 7: ...28 5 87 6 11 Water Flow Rate 82 71 C kg s 3 4 4 3 5 4 6 5 8 2 9 2 10 9 13 0 17 4 21 7 Hydraulic Resistance at 80 60 C kPa 0 2 0 3 0 4 0 6 0 6 0 8 1 1 1 6 1 8 1 9 Water Flow Rate 80 60 C kg s 1 9 2 4...

Страница 8: ...40 235 235 235 235 235 235 275 Connections 1 Flow PN6 DN50 DN80 DN80 DN80 DN80 DN80 DN80 DN100 2 Return PN6 2xDN50 2xDN80 2xDN80 2xDN80 2xDN80 2xDN80 2xDN80 2xDN100 3 Safety valve BSP G1 1 2 G2 G2 G2...

Страница 9: ...peration Connections 800 1000 1 Flow PN6 DN125 DN150 2 Return PN6 2xDN125 2xDN150 3 Safety valve BSP G2 G2 4 Drain BSP 2xG1 1 2 2xG1 1 2 5 Stat pockets BSP 2xG1 2 2xG1 2 6 Pressure switch BSP R3 4 R3...

Страница 10: ...he boiler to suit specific plant room layout See Page 11 for a typical plant room layout Cyclone 800 1000 A mm 1389 1439 B mm 744 768 C mm 2368 1540 D mm 2227 2422 E mm 2615 2872 F mm 900 950 G mm 274...

Страница 11: ...mensions and Technical Information Typical Layout Hoval STU Boiler with modular twin cyclone floor mounted ID fan and connecting ductwork Hatched ducting NOT by Hoval To suit specific plant room layou...

Страница 12: ...iltration in use The elements are easily replaced by vertically removing the existing elements from the unit and replacing with a new element Accordingly it is essential to locate the filter with a mi...

Страница 13: ...ught Fan Incoming Electrical Supply Type Motor kW Absorbed power kW STU 150 CF 150 Halifax 1 5 0 89 3N 50Hz 400 230V 10A max STU 200 CF 200 Halifax 1 5 0 86 3N 50Hz 400 230V 10A max STU 250 CF 250 Hal...

Страница 14: ...CF Biomass Filter Typical units 14 Measurements in mm CF 500 unit Clearance of 1000mm required above the unit for filter withdrawal replacement...

Страница 15: ...spection lids Cladding and Lagging 75mm thk Control panel RCA 25 DD pulse valve Compressed air reservoir Particulate discharge tray Clearance of 1000mm required above the unit for filter withdrawal re...

Страница 16: ...outlet Outlet Outlet Fluing to chimney Typical Layout STU 200 Wood Pellet Boiler with CF 200 Biomass Filter Hatched ducting not by Hoval Note easy radius bends should be used 16 Side Elevation View o...

Страница 17: ...ke build bunker store These typically require a larger floor area and are less effective in terms of the available recoverable volume of fuel Some profiling of the bunker base should be considered min...

Страница 18: ...l consumption would be estimated based on the loading placed on the boiler Wood Pellet fuel store to be sized to accommodate a minimum of 10 15 days anticipated fuel use 3 Delivery Size The fuel suppl...

Страница 19: ...s of dead volume b Slots active pick up locations c Gate valve required to isolate individual silos 2 STU wood pellet boiler 3a Flexible auger Note requirements for long radius bends 1 5 2m Note maxim...

Страница 20: ...20 Hoval STU Wood Pellet Boiler Typical Plantroom layouts GENERAL ARRANGEMENT OF A STOKER AND A FABRIC SILO GENERAL ARRANGEMENT OF STU BOILER WITH TWIN EB BOOT TABLES AND PROFILING...

Страница 21: ...21 Hoval STU Wood Pellet Boiler Typical Plantroom layouts GENERAL ARRANGEMENT OF STU BOILER AND A FABRIC TROUGH BUNKER INDICATIVE LAYOUT OF STU BOILER WITH GRP SILO...

Страница 22: ...lock nuts on the new hinge side are fully tightened 5 Loosen locknuts on the new opening side so that a seal is obtained all round the fibre joint Important Always have two nuts tightened to prevent t...

Страница 23: ...idelines The supply of air to a space housing the boiler by mechanical means should be mechanical inlet with natural or mechanical extraction Mechanical extract ventilation with natural inlet must not...

Страница 24: ...is particularly important on any horizontal section The flue should include some pressure relief and or draught stabiliser as Appropriate Flues should be supported independently to prevent any undue...

Страница 25: ...ains is treated Even the water in closed systems will promote corrosion unless treated For these reasons Hoval strongly recommend that when necessary the system be thoroughly cleaned prior to the use...

Страница 26: ...e starting the ignition process The Stoker Control Panel also houses a series of indicator lights as follows Panel Live Orange Fuse Failed Red Stoker Run Green High Limit Red Trip Red Under normal ope...

Страница 27: ...en stoker running but the error message will still be retained on the display until cleared by the operator This is accessed via the manual status menu as detailed on page 28 However it is important t...

Страница 28: ...eters and manually set plant status only Level 2 As Level 1 and change times schedules set points view menus Level 3 As Level 2 with change all settings and view all parameters Level 4 As Level 3 with...

Страница 29: ...using the controller The parameters shown here will be directly related to your plant applications and requested access levels to suit your experience These parameters may be changed by you e g if a s...

Страница 30: ...ndicated whether the Boiler Fan is called to run I On O Off Delayed FD Fan All Levels Indicates whether the Stoker Fan is called to run I On O Off Trickle Feed Rate Level 4 This sets the pellet feed t...

Страница 31: ...All other manufacturers equipment has been installed and commissioned e g pressurisation units A suitable safety valve has been fitted to the boiler together with associated discharge pipework Suffici...

Страница 32: ...ting The boiler will be left with water in the water dump device full to within 50mm of the top of the container The LRP boiler control thermostat is adjusted to suit the system design flow and temper...

Страница 33: ...t excessive manual input The stoker will automatically adjust the firing range to match the load with damper control on both the forced and induced draught fans Continuous O2 monitoring of the flue ga...

Страница 34: ...ition of the fire within the retort to ensure that combustion is fully established using the sight glass on the front of the door of the boiler IMPORTANT Once the fire has established the isolating sw...

Страница 35: ...D FAN only switch should be put to the ID fan only position to pull any residual fumes out of the boiler On the 600 1000kW boilers the boiler needs to be left to stand for 30 minutes The boiler door c...

Страница 36: ...correctly NOTE No continuous make up of water should be taking place In this event check where a leak may be occurring or if pumping over is taking place Maintenance Boiler and Stoker Servicing In ad...

Страница 37: ...so that the shear pin slot is at the top using the shear pin bar provided align the slot on the worm section remove broken pin and fit replacement If there is a jam or pin failure on the Pick Up Auge...

Страница 38: ...38 Hoval STU Wood Pellet Boiler GRP SILO SPECIFICATION SHEET 2 85m Appendix A...

Страница 39: ...39 Hoval STU Wood Pellet Boiler Appendix B Note The thermostatically operated valve has a red test button which will prove the valve opens when pressed held in...

Страница 40: ...this sleeve to ensure correct operation of the wa ter dump device Removable cap Water dump container Boiler drain connection two per boiler Water dump thermal valve preset to open at 95 C Thermal valv...

Страница 41: ...thermostat access cover Isolate the boiler control panel via the main isolator switch on the panel facia before removing this cover Remove cap and check the water level weekly Water should be within 5...

Страница 42: ...amiliarisation Information Pellet Drop box Proximity level switch in pellet delivery auger transfer box Access cover to delivery auger to drive coupling shear pin Stoker delivery auger to drive coupli...

Страница 43: ...nduced Draught Fan Actuator for Induced draught fan damper Smoke box condensate drain piperwork with trap Mains cold water supply Thermal valve preset to open at 95 C Cooling coil heat exchanger s con...

Страница 44: ...Combustion chamber pressure sensing point with interconnecting pipework to pressure switch Clean this out weekly Appendix C Boiler Familiarisation Information Forced draught fan with motorised damper...

Страница 45: ...oiler Familiarisation Information View of Combustion Chamber with pellets in the retort at the correct level for lighting Refractory fibre boiler door lining Cut out for sight glass opening Combustion...

Страница 46: ...hanger Appendix C Boiler Familiarisation Information Remove insulated red cover below boiler door and lift off metal in spection panel to gain access to the optional 3kW electric ignition unit located...

Страница 47: ...47 Hoval STU Wood Pellet Boiler Appendix C Boiler Familiarisation Information Optional 3kW electric ignition unit Lift off metal inspection panel...

Страница 48: ...tch the Wood burner to the Off position found on the KINDLE OFF AUTO selector switch mounted on the control panel 3 Turn the separate I D Fan selector switch to I D Fan Only 4 Take care when opening t...

Страница 49: ...sealed when refitted 8 Refit the spiral retarders 9 Clean the small hole for the combustion chamber pressure switch sensing point which is found on the L H S of the combustion chamber close to boiler...

Страница 50: ...k on 8 If the fire is not established allow more time before turning the Pick up and Conveyor augers back on NOTE For a boiler fitted with an ignition system the above procedure should only be employe...

Страница 51: ...rruption Burn back Fire has tracked back along the Thermostat initiation conveyor tube Possible causes are Conveyor motor tripped see below or shear pin failure burn back thermostat malfunction or a p...

Страница 52: ...52 Hoval STU Wood Pellet Boiler Notes...

Страница 53: ...53 Hoval STU Wood Pellet Boiler Notes...

Страница 54: ...thgate Newark Notts NG24 1JN Tel No s 01636 59413 or 593435 Service Desk direct dial numbers 01636 593412 Spares Desk direct dial Fax 01636 673532 e mail service hoval co uk spares hoval co uk STUman...

Отзывы: