9
Hoval STU Wood Pellet Boiler
Dimensions and Technical Information
Key:
1
Flow
2
Returns, one either side, both
to be connected to a common
inlet header
3
Safety valve connection
4
Drain connections (plugged)
5
Stat & modulating sensor
mounting sockets
6
Combustion chamber pressure
switch connection
7
Smoke box condensate drain
8
Cooling coils c/w temp sensor
9
Temperature gauge
10
Smoke box cleaning doors
11
Sight glass assembly
12
Twin delivery augers
13
Burn back Stat (one per stoker)
14
Burn back water dump (one per
stoker)
15
Temp. sensor for water dump
device (one per stoker)
16
Boiler door Microswitch
17
Common transfer box with two
No. proximity sensors
18
Motorised burnback protection
damper
19
Combustion Chamber Pressure
switch
Notes:
• Thermal safety heat exchanger connections c/w thermostatic
control valve connection (3/4") to be connected to a cold water
mains supply. Drain pipework (by others) to be run via tundish
to drain. See Appendix B, for further details.
• Boiler mounted control panel not shown but the typical size for
models 800 and 1000: 800mm W x 1200mm H x 300mm D
This may change and should be checked on a site by site basis.
Connections:
800
1000
1 Flow
(PN6)
DN125
DN150
2 Return
(PN6) 2xDN125 2xDN150
3 Safety valve
(BSP)
G2
ײ
G2
ײ
4 Drain
(BSP) 2xG1.1/2 2xG1.1/2
5 Stat pockets
(BSP) 2xG1/2"
2xG1/2"
6 Pressure switch (BSP)
R3/4"
R3/4"
7 Smoke box drain (mm)
G3/4"
G3/4"
8 Cooling Coils
(mm)
G3/4"
G3/4"
STU Boiler
800
1000
A
(mm)
-
-
B
(mm)
3134
3282
C
(mm)
1540
1540
D
(mm)
2530
2713
E
(mm)
2962
3110
F
(mm)
710
723
G
(mm)
1195
1150
H
(mm)
1060
1060
J
(mm)
285
285
K
(mm)
441
441
L
(mm)
200
200
M
(mm)
1284
1299
A 3ph + N 32A 400V supply is
required for the control panel
operation.
An automatic air vent, should be fitted by
the installer at high level on the flow
pipework connecting to the boiler.