Hoval SR-plus 1200 Скачать руководство пользователя страница 22

22

Maintenance - Burners

Burner Maintenance

Impor-

Before carrying out any work on the burner ensure that the main electrical isolating switch is 

in the OFF position and the fuel isolating valve closed.

These instructions are provided for the benefit of the 

operator and are intended to be of assistance in making 

minor adjustments and provifing the burner with proper 

maintenance,  cleaning  and  lubrication.   Additional 

information can be obtained through your installer or 

from the manufacturer.

• 

Fuel

  The  unit  is  designed  to  burn  the  fuel  stated  on

  the  burner  nameplate.    Under  no  circumstances

  must  any  other  type  of  oil  or  gas  be  used.

  In the case of burner fuel conversion, check to see

  that the fuel used corresponds with that marked on

  the new burner nameplate.

• 

Starting and Stopping

• 

Emergency Stop

  The burner can be stopped in an emergency by

  switching off the mains isolating switch provided on

  the line between the burner and the electric supply.

  The installer must identify the switch.  Check position

  of  this  switch  or  any  "panic  button"  available.

•  Check the Burner Operation

  Inspect burner flame periodically.  If it becomes lop

  sided or there is any noticeable change in flame

  colour, call the service engineer.

  When cleaning the room housing the heater unit,

  always switch off the burner to reduce the amount

  of dust and lint drawn in through the air inlet.

• 

Preventive Maintenance

  Consult your heating engineer for advice on regular

  prevetive maintenance intervals.

• 

Gas Supply

  Should the gas supply be interrupted, the system

  may  require  venting  of  air  that  may  have 

  accumulated, before the burner is restarted.  This

  is achieved by unscrewing the pressure test point

  situated  down-stream  of  the  main  govenor  or

  combination valve and venting the air to atmosphere

  until gas has reached the test point.

 

WARNING: No smoking or naked lights to be

   

allowed  as  a  gas/air  mixture  is

   

dangerous.

  Periodical  examination  of  all  pipework  should

  be  carried  out.    The  recommended  method  is

  to  brush  a  soap  solution  around  all  the  jointed

  areas.   A  leak  in  the  system  would  have  the 

  effect of forming bubbles.

  CAUTION:  Do not place any items in the boiler

   

combustion  chamber  as  it  is  not

   

suitable for burning waste.

• 

Oil pump

 

  See burner manufacturers manual.

• 

Gas train items and gas leak detectors

  For  maintenance  of  these  units  refer  to  the

  manufacturers manual.

• 

Motor

  Keep the burner motor clean and dry.  Any deposits

  of dust or lint should be blown out occasionally.  On

  motors provided with oiling holes, a few drops of

  high quality SAE 20 oil should be injected every six

  months.    Surplus  lubricant  spreading  from  the

  bearings should be wiped away.  Some motors have

  sealed-for-life  bearings;  these  require  no

  maintenance.

• 

Fan Runner

  Keep the fan blades clean and free from oil and

  build up of dust or deposits picked up from a dusty

  boilerhouse.

• 

Oil Strainer/Filter

  Replace filter element anually.

• 

Nozzles, Flame Plate and Electrodes

  Maintenance by the boiler operator is usually limited

  to checking the condition of these items only whilst

  the boiler door is open.  Servicing the oil or gas

  nozzle,  which  may  require  dismantling,  and

  replacement of parts should be left to the service

  engineer.

  The boiler operator may wipe off deposits of soot

  and oil from the flame plate and nozzle taking care

  not to disturb the parts.  Check the electrodes are

  set  correctly  after  referring  to  the  burner

  manufacturers manual.

• 

Flame Sensor

  Remove and clean the flame sensor which is an

  ultraviolet cell for gas or photo-electric cell for oil

  with methylated spirit on a lint free cloth.  Do not

  handle window of the flame sensor after cleaning.

  NOTE: 

Remove  the  flame  sensor  before

   

 

attempting to remove the burner inner

   

 

assembly.

August 2014

Содержание SR-plus 1200

Страница 1: ... Issued By TECHNICAL DEPT Dated August 2014 Approved KS Operating and Installation Instructions for the SR plus hot water boiler 0088 ...

Страница 2: ...Filling the system with water water treatment Burner matching Fitting the Burner Water flow return temperatures Control details Boosters Commissioning Operating Instructions including sequencing of boilers under BMS control Maintenance Inspection Servicing Boiler Burner Servicing Summer Shutdown Burner Maintenance Oil Burner Fault Finding Chart Gas Burner Fault Finding Chart 3 4 4 4 5 6 8 9 15 9 9...

Страница 3: ...d burner reference number These numbers are indicated on the appropriate nameplates For completion by Plantroom Attendant Boiler Model Burner Ref No Output kW Fuel K No Commissioning Date For technical servicing or parts enquiries telephone fax or e mail to Hoval quoting the boiler s serial number as above The installation should be in accordance with current I E E Regulations relevant British Sta...

Страница 4: ...ance with relevant British Standards the Gas Safety Regulations Building Regulations I E E Regulations and the by laws of the local Water Authorities A flat level fire proof floor should be provided and the location should permit the provision of a satisfactory flue system and adequate air supply Gas Safety Nameplate Delivery General BS6644 Installation of Gas Fired BS6880 LowTemperature Hot Water...

Страница 5: ...ture is governed by the pressure available at the highest point of the system Take the 17o C anti flash margin from the saturated temperature of steam at that pressure to find the maximum operating temperature Door Hinging The hinged side door nuts are supplied with a locknut at the back of the door boss Hoval should be advised of the door and gas burner handing when the boiler is ordered or at th...

Страница 6: ...T m3 h 21 50 25 80 32 24 42 99 53 74 64 49 Boiler water content litres 800 770 1340 1250 1320 1330 Dry Weight without burner 6 kg 1700 1754 2463 2616 3350 3650 Type 1750 2000 2250 2500 3000 3500 4000 Maximum output kW 1760 2050 2350 2650 3000 3500 4150 Minimum output kW 880 1025 1175 1325 1500 1750 2075 Boiler input at maximum output kW 1931 94 2242 89 2573 93 2908 89 3285 87 3837 72 4555 43 Boile...

Страница 7: ... equipment ie gas booster separate oil pump etc should be isolated via the same switched isolator 2 L D F J H G C M E 3 8 4 9 9 Burner CL 1 6 5 7 Elevation view N 205 SR Plus Model kW Rating at high A B C D E F G H J L M N Flow return BS4504 PN16 Safety valve Flue I D Dry Weight kg Water Content litres 500 411 500 1413 1262 2323 1958 766 190 1320 920 280 766 1486 1371 100 N B R 2 250 1700 800 600 ...

Страница 8: ...y Weight kg Water Content litres 1200 1151 1250 1626 1500 2909 2514 876 220 1795 1345 380 876 1745 1630 125 N B R2 350 3350 1320 1500 1426 1500 1722 1590 2909 2514 927 220 1806 1356 466 927 1833 1718 150 N B R2 400 3650 1330 1750 1625 1760 1852 1720 3361 2966 992 220 2137 1687 500 992 1990 1875 150 N B 100 N B 400 4325 2150 2000 1900 2050 1952 1820 3381 2966 1042 240 2137 1687 590 1042 2090 1983 1...

Страница 9: ...ation through the walls and air ventilation openings 3 From the chimney outlet e g where dwellings are located very close by the boilerhouse or above the chimney outlet Natural gas fired plant has low frequency sound pressure levels which are disturbing to nearby residents when the boilers are operating particularly at night The following are sound and vibration control measures which can be taken...

Страница 10: ...ural or mechanical extraction Mechanical extract ventilation with natural inlet must not be used Any mechanical means of entering air into a basement boilerhouse should have a balancing outlet so that the air pressure in the boilerhouse does not exceed 0 05 W G 12 5 Pa Where mechanical inlet and mechanical extract system is applied the design extraction rate should not exceed one third of the desi...

Страница 11: ...correct combustion and high efficiency to reduce running time to a minimum and to maintain low levels of CO2 Greenhouse effect CO and NOx d a n g e r o u s g a s e s C u r r e n t regulations for NOx limits 1993 are maximum 260 mg kWh 148ppm at 0 O2 Burners supplied with Hoval boilers fully meet this requirement Adequate doors should be provided in flues and chimneys for cleaning and inspection pu...

Страница 12: ...ssion There will always be corrosion within a heating hot water system to a greater or lesser degree irrespective of water characteristics unless the initial fill water from the mains is treated Even the water in closed systems will promote corrosion unless treated For these reasons Hoval strongly recommend that when necessary the system be thoroughly cleaned prior to the use of a stable inhibitor...

Страница 13: ...es so that the pump does not overheat Gas burner valve trains should be located within 300mm of the burner and supported independently of the boiler at the opposite side to the door hinge so that the door can open after breaking a connecting joint Sealing of the burner draught tube A small annular space is necessary around the burner draught tube in the door refractory to enable the burner to be w...

Страница 14: ...rtment Terminals Terminals are provided in the control panel for linking in additional controls e g time switch pressurisation unit interlocks etc The control panel as illustrated is generally supplied for mounting on top of the boiler casing by the installer For normal high low operation the control stat is set by the Hoval commissioning engineer at the required lev el e g 80o C The limit stat wi...

Страница 15: ...tion should be given to the use of a purpose designed bypass to dissipate the excess heat and the installation of a twin duty stand by system to allow for regular inspection Where a stand by booster is fitted it should be operated regularly or in rotation If the booster is operating in rotation auto cycling may have been installed as an option Important If a vital function is served install a stan...

Страница 16: ... chimney if fitted are in the open position and locked open if manually operated and if electrically operated that the burner is interlocked electrically to prevent operation until the damper is open the electrical installation with the appropriate wiring diagram for the boiler and burner and for correct fan rotation correct direction of flow in the gas line correct operation of the gas booster if...

Страница 17: ...ter that the boiler is fired up at a rate allowing the door refractory to reach a uniform temperature through its thickness thereby preventing any damage burner is adjusted to give optimum combustion together with flame shape and penetration the Heating Engineer will have the opportunity to receive instruction on the correct operation of the plant during commissioning and to aquaint himself with t...

Страница 18: ...pared operating and maintenance instructions specifically for the whole plant those instructions should be referred to in the first instance Instruments and Controls Instruments are generally mounted at the top front of the boiler A boiler flow water thermometer will always be present an altitude gauge may also be provided The basic controls for any boiler will be a A sequence control box mounted ...

Страница 19: ...of damage or leakage and for security In an open vented heating system check Level of water in the feed and expansion tank That the ball valve is free to operate correctly All air vents are operating correctly NOTE No continuous make up of water should be taking place In this event check where a leak may be occurring or if pumping over is taking place On the boiler door examine the ceramic strip s...

Страница 20: ... to clean a warm boiler 2 Switch OFF electrical supply to the burner Where a plug connection is fitted in the cable from the boiler to the burner disconnect at this point Switch OFF electrical supply to the booster 3 Turn OFF all fuel shut off valves at the burner 4 Where rigid fuel pipes to burner are employed e g gas burners disconnect pipe s to allow the boiler door to open 5 Fully open the boi...

Страница 21: ...Summer shut down 11 If disconnected plug in the boiler burner electrical connection 12 Check boiler door is effectively closed ineffective closure will be detectable by sight or smell 13 It is recommended that when the boiler has become thoroughly hot a combustion efficiency check is made by the Service Engineer 14 If the boiler is not immediately to be used switch OFF electrical supply to burner ...

Страница 22: ...r to atmosphere until gas has reached the test point WARNING No smoking or naked lights to be allowed as a gas air mixture is dangerous Periodical examination of all pipework should be carried out The recommended method is to brush a soap solution around all the jointed areas A leak in the system would have the effect of forming bubbles CAUTION Do not place any items in the boiler combustion chamb...

Страница 23: ...e preheating equipment is operating 1 Switch off burner Check spark plug gap Check H T leads and connections Check and clean ignitionelectrode s andinsula tor 2 Opendoorandcheckwhether oil has been sprayed into combustion chamber if no evidence of spray clean or replace burner nozzle s 3 Check as above If no spray c h e c k t h e f o l l o w i n g a There is oil in the fuel tank b All necessary va...

Страница 24: ...d or restricted Flue damper closed 7 Burner draught tube or flame plate misplaced or faulty 8 Door refractory failure Action 1 Clear obstruction 2 Reset damper and make a combustion check special instruments required 3 Replace nozzle s 4 Replace with correct nozzle s 5 Reset pump pressure regulator 6 Clean tubes Open flue damper and check why it became closed Clear blockage or restriction 7 Call S...

Страница 25: ...tra violet cell fault Action 1 Check a Main isolator switch is on and power is available at the control panel b Overload protective devices of burner motors if fitted 2 Switch contacts must be in the burner start position Check switch is not stuck in the satisfied position 3 Check a That all switches are closed b Booster is not locked out due to low inlet gas pressure and that pressure switches fu...

Страница 26: ...erheated 4 Gas pressure alteration 5 Boiler tubes flue or chimney blocked or restricted 6 Door refractory failed Action 1 As B3 2 Clean cell and check correctly inserted facing the flame 1 Switch OFF burner and check pipelinejointswithsoapsolution 2 Closepilotmanualvalveandthen main manual valve at the burner toseeifthisisolatestheproblem Call gas engineer to check the automaticvalves Donotoperate...

Страница 27: ...Conservation of Energy Protection of the Environment Hoval Limited Northgate Newark Notts NG24 1JN Telephone 01636 672711 Fax 01636 673532 e mail service hoval co uk Web Site www hoval co uk March 2014 ...

Отзывы: