Options
The following optional components are supplied separately:
■
Fresh air and exhaust air silencer
(on separate pallet; bolts, hinges and screws enclosed)
■
Additional room air temperature sensors, combination sensor room air quality,
temperature and humidity (in zone control panel)
■
Version with 2 Air-Injectors or without Air-Injector:
A supply air temperature sensor is enclosed behind the extract air grille.
Notice
Below-roof units with a connection module of length V3 are shipped
horizontally. In this case, loose parts are not placed behind the extract air
grille but behind the extract air access door in the roof unit.
Preparation
■
The units are delivered screwed onto the pallet. To loosen the screws, the
inspection doors must be opened. When unloading the units, make sure that
there is enough space to open the inspection doors.
■
Use a forklift with a sufficiently long fork to unload (at least 1.8 m).
■
Check the consignment against the delivery documents and the order
confirmation to ensure that it is complete. Report missing parts and any
damage immediately in writing.
7.2 Storage
If you do not install the unit immediately:
■
Remove the packaging film to avoid water vapour condensation.
■
Store the unit in a dry, dust-free room.
■
Keep the storage temperature between – 10 °C and + 50 °C.
■
Avoid too long storage periods. After a storage period of more than 1 year:
– Check that the bearings of the fans move smoothly before installing the unit.
21
RoofVent
®
KG
Operating instructions
Transport and installation
4 220 755-en-00