ALARM MESSAGES
79
4 213 563 / 03
7.4
Instructions in the event of faults
1. If the heat generator does not start check if the blocking switch is set to “I”.
2. For resetting the fault, see below (point 7.5).
3. Pressing the alarm message icon allows the alarm messages to be requested
(see also points Pkt. 7.1 and 5.6.1).
7.5
Resetting the faults
Fig. 01
Blocking switch Fault lamp
Reset button
Alarm message icon
(show alarm messages)
LED indicator
Hinged cover
Faults can be recognised by the alarm message icon and/or by a red-orange flashing LED indicator to the left of the
operating field (see also point 5.6.1 page 17, Pos. 6).
If, in addition, the fault lamp next to the blocking switch lights up, the heating operation was stopped. The fault can be
acknowledged by pressing the reset button.
The reset button is allowed to be pressed once at most.
If the failure indication lamp continues to be lit, please
contact Hoval Customer Service.
1. Open the Hinged cover (Fig. 01) on the right of the control panel.
2. Press the reset button for 3 seconds. If the fault lamp goes out, the heat generator carries out a start attempt. If
the fault lamp does not go out or lights up again after the start attempt, please contact Hoval Customer Service.