2.7
Fitting the neutralisation box and the con-
densate delivery pump (option)
1.
Fit condensate delivery pump (1, Fig. 23) as shown
in the drawing. Route the cable to the controller and
connect according to the diagram.
1
Fig. 23
2.
Remove the neutralisation box from its packaging.
Remove the front and rear cover of the neutralisation
box. Empty the neutralisation granulate into the neut
-
ralisation box (Fig. 24) and distribute evenly.
neutralisation granulate
front
2
Fig. 24
3.
Remove front cover (2a, Fig. 25). Release lateral lo
-
cking bolt (2) (turn approx. ¼ to the left and pull out as
far as the stop). Lift the front cover straight upwards
and remove towards the front.
4.
Remove base plate (3). Lift base plate straight up
-
wards and remove.
2
2a
3
Fig. 25
5.
Fit rear cover (4, Fig. 26) of the neutralisation box.
6.
Fit jubilee clip (5) approx. 20mm from the upper end
of the hose and tighten slightly. The hose (5a) of the
connection eccentric (5b) must be aligned towards
the left.
5
4
5a
5b
Fig. 26
12
4 213 784 / 00
ASSEMBLY
Содержание 41-UltraOil 16
Страница 35: ...35 4 213 784 00...