background image

12

installation

 & 

operation

 

manual

 | 

ocle

/

ocla

 

heating

 

system

 

3.3 

HEATING SYSTEM START-UP

WARNING

!

Hazardous voltage: 

Before wiring, servicing or 

cleaning the heating system, turn off the power 
and follow your organization’s lockout and tagout 
procedure. Failure to do so could allow others to turn 
on the power unexpectedly, resulting in harmful or 
fatal electrical shock.

NOTICE

Pump damage: 

Do not run the motor/pump assembly 

dry for more than five seconds at a time. Running a 
pump that is not completely filled with fluid will cause 
damage to the pump seal.

Proper heating operation:

 The high-limit temperature 

control relay (TCR2) must be set at least 18 

°

F (10 

°

C) 

higher than the control temperature control relay (TCR1) 
for proper heating operation. This will prevent nuisance 
tripping of the high-limit circuit.

3.3.1  FIRST RUN PROCEDURE

1. 

For three-phase applications, ensure a motor 

rotation check has been performed prior to 

introducing fluid to the pumps (

see 

SECOIO  

2.6.3

). 

 OOE:

 

  Single-phase systems are prewired to 

ensure the pump motor rotates in the 

correct direction. A motor rotation check is 

not necessary for single-phase systems.

2. 

Check and tighten all electrical and plumbing 

connections.

3. 

Ensure isolation valves are 

open

 before energizing 

the system.

4. 

Bleed all trapped air from the heating system by 

opening a plug or pipe fitting at or near the pump. 

Press and hold the 

prime

 button to evacuate any 

remaining air in the lines.

 OOE:

 

  When priming the pump, the pressure 

gauge should indicate an increase in 

pressure. Your system’s operating pressure 

may vary depending on the configuration 

of the engine.

5. 

Turn the 

local

/

off

/

remote

 switch to 

local

 or 

remote

 to energize the heating system.

6. 

Once operation is satisfactory, turn the control 

dial on the temperature control relay TCR1 to 

the desired temperature setting for engine oil. 

HOTSTART recommends a control temperature on 

TCR1 of 104 °F (40 °C). The high-limit temperature 

setting on TCR2 should be set at 194 °F (90 °C). 

See 

SECOIO  3.2.2

 

and 

SECOIO  3.2.3

.

7. 

Turn the 

local

/

off

/

remote

 switch to 

remote

 to 

verify the 24 V DC remote signal connection  

(if installed).

MAINTENANCE, 

REPAIR AND 

TROUBLESHOOTING

4.1 

SYSTEM FAULTS

A failure in the pump motor that causes the motor 

protection switch (MPS1 or MPS2) to trip will shut 

down the respective heating system. A fault signal 

will be transmitted. If this failure occurs, the 

local

/

off

/

remote

 switch must be switched to 

off

 and the 

operator must press the 

reset

 

button (or the MPS reset/

on button) to reset the fault. (

See 

SECOIO  3.1.3.

)

If there is a failure that causes a high temperature to 

occur, the high-limit temperature controller (TCR2 or 

TCR4) will shut down the respective heating system, 

including the pump motor. A fault signal will be 

transmitted. To restart the system, the 

local

/

off

/

remote

 switch must be switched to 

off

 and then back 

to 

local

 

or 

remote

 to resume operation once the 

fluid temperature drops below the high-limit preset (

See 

SECOIO  3.2.3

.

). For additional troubleshooting, 

see 

SECOIO  4.5

.

4.1.1  COOLANT FAULTS

A fault signal will be transmitted if:

• 

The coolant pump motor protection switch is 

tripped (MPS1).

• 

The coolant high-limit temperature is 

exceeded (TCR2).

4.1.2  OIL FAULTS

A fault signal will be transmitted if:

• 

The oil pump motor protection switch is 

tripped (MPS2).

• 

The oil high-limit temperature is exceeded 

(TCR4).

Содержание OCLA

Страница 1: ...216272 000 rev6 INSTALLATION OPERATION MANUAL MODEL OCLE OCLA DUAL FLUID CIRCULATING HEATING SYSTEM FOR HAZARDOUS LOCATIONS ...

Страница 2: ... this page intentionally left blank ...

Страница 3: ...g our customer service department at 509 536 8660 Have your model number and serial number ready when contacting the warranty department COPYRIGHT Hotstart Manufacturing Inc is the owner of all trademarks and copyrightable material contained herein all rights are reserved no form of reproduction is authorized without prior written consent from Hotstart Manufacturing Inc NOTE Typical heating system...

Страница 4: ...llers and operators of this equipment must be thoroughly familiar with the instructions in this manual before commencing work Hot surfaces Avoid contact with the system while it is in service Some surfaces may remain hot even if the system is not energized Proper lifting Use proper lifting equipment and rigging to move this equipment Create a plan before attempting to move Proper lifting locations...

Страница 5: ... Temperature Gauge 10 3 1 5 Coolant Pressure Relief Valve 10 3 1 6 Oil Pressure Relief Valve 10 3 2 SYSTEM COMPONENTS 11 3 2 1 Motor Protection Switch 11 3 2 2 Control TCR Temperature Control Relay 11 3 2 3 High Limit TCR Temperature Control Relay 11 3 3 HEATING SYSTEM START UP 12 3 3 1 First Run Procedure 12 4 MAINTENANCE REPAIR AND TROUBLESHOOTING 12 4 1 SYSTEM FAULTS 12 4 1 1 Coolant Faults 12 ...

Страница 6: ...iv installation operation manual ocle ocla heating system this page intentionally left blank ...

Страница 7: ...witch C Coolant prime button D Oil prime button E Coolant reset button F Oil reset button G Coolant outlet 1 NPT H Oil outlet 1 NPT I Coolant high limit resistance temperature device RTD J Oil high limit resistance temperature device RTD K Identification plate L Coolant pressure temperature gauge M Pressure relief valve 0 5 NPT N Oil pressure temperature gauge O Coolant control resistance temperat...

Страница 8: ... and forces it through the heating tank to the oil return line The coolant pump and oil pump will continuously circulate fluid throughout the engine To maintain consistent fluid temperature the heating elements will cycle on and off at the user selected temperature control point A coolant check valve included with the OCLE OCLA unit and installed at the coolant outlet and an oil check valve user s...

Страница 9: ...sed to fill the lines and heating tank Do not operate the heating system without the presence of fluid Position the heating tank to ensure it is completely full of fluid while in operation Pump priming Fill supply line with fluid Pump is not self priming Fluid must be present in the pump before start up Trapped air inside the pump will cause pump and seal damage Pump seal damage Do not reduce the ...

Страница 10: ...et 1 5 meters To minimize flow restriction HOTSTART recommends using sweeping bends or 45 fittings At a minimum size the oil supply line per the pump inlet NOTICE Do not reduce the supply line inner diameter pump seal damage will occur NOTE To maximize flow and allow the longest possible supply line install the largest practical inner diameter hose for most installations HOTSTART recommends using ...

Страница 11: ...TION PORT SECTION 2 1 1 CHECK VALVE SECTION 2 1 1 ISOLATION VALVE ISOLATION VALVE OIL SUPPLY SECTION 2 1 1 OIL RETURN SECTION 2 1 2 E 2 E 1 V 2 V 3 V 1 COMPONENT DESCRIPTION V 1 USER SUPPLIED CHECK VALVE V 2 USER SUPPLIED FULL FLOW ISOLATION VALVE E 1 OIL PUMP E 2 OIL HEATING ELEMENT V 3 USER SUPPLIED FULL FLOW ISOLATION VALVE ...

Страница 12: ... point at the suction side of the engine water pump A NOTICE At a minimum suction port must be sized per the pump inlet 1 25 NPT To minimize flow restriction the coolant supply line must be as short and as straight as possible Use elbow fittings sparingly HOTSTART recommends using sweeping bends or 45 fittings NOTE For optimal pump performance HOTSTART recommends a minimum of 6 inches 152 mm of st...

Страница 13: ...E PORT SECTION 2 3 2 ISOLATION VALVE ISOLATION VALVE COOLANT RETURN SECTION 2 3 2 COOLANT SUPPLY SECTION 2 3 1 PRESSURE RELIEF VALVE SECTION 2 3 3 E 2 E 1 V 1 V 3 V 2 COMPONENT DESCRIPTION V 1 V 2 USER SUPPLIED FULL FLOW ISOLATION VALVE E 1 COOLANT PUMP E 2 COOLANT HEATING ELEMENT V 3 USER SUPPLIED FULL FLOW ISOLATION VALVE PRESSURE RELIEF VALVE ...

Страница 14: ...t procedure Failure to do so could allow others to turn on the power unexpectedly resulting in harmful or fatal electrical shock Electrical hazard All wiring shall be done by qualified personnel in accordance with national state and local codes Each system shall be grounded in accordance with the National Electrical Code Failure to properly ground the system may result in electrical shock 2 6 1 MA...

Страница 15: ...nt the pump motor is not running Switch Location Signal X1 7 X1 8 X1 9 coolant H X2 7 X2 8 X2 9 oil I The switch location signal indicates the local off remote switch position off 7 local 8 remote 9 L1 L2 TB1 L3 A B Figure 5 Main power supply and customer interface connections as shown in the OCLE OCLA control box Reference electrical schematic drawing for proper wiring locations the following ill...

Страница 16: ... the prime button to energize the pump motor in order to remove any air in the heating system without energizing the elements NOTICE Do not run the motor pump assembly dry for more than five seconds at a time NOTE The prime function is intended for use during the first run procedure see SECTION 3 3 1 or after performing maintenance on the heating system or plumbing see SECTION 4 3 3 1 3 RESET BUTT...

Страница 17: ...F 40 C See Fig 7 3 2 3 HIGH LIMIT TCR TEMPERATURE CONTROL RELAY The high limit TCRs TCR2 and TCR4 are a protection device to prevent fluid overheating The high limit TCR uses a resistance temperature device RTD located near the tank outlet The default setting for the coolant and oil high limit TCR is 194 F 90 C and should always be at least 18 F 10 C higher than the corresponding control TCR set p...

Страница 18: ...epending on the configuration of the engine 5 Turn the local off remote switch to local or remote to energize the heating system 6 Once operation is satisfactory turn the control dial on the temperature control relay TCR1 to the desired temperature setting for engine oil HOTSTART recommends a control temperature on TCR1 of 104 F 40 C The high limit temperature setting on TCR2 should be set at 194 ...

Страница 19: ... voltage switching controls for motors and heating elements in HOTSTART heating systems The contactors use 120 volt or 240 volt coils To test for failure check for continuity across the coil connections an open or direct short reading indicates a failed contactor coil The contacts on the magnetic contactor should be inspected periodically for welding arc erosion and mechanical wear If any of these...

Страница 20: ...contact HOTSTART for further assistance h h If there is no continuity between TCR terminals T2 and T3 locate connected RTD on the heating tank Unscrew the RTD plug from RTD See Table 2 and Fig 10 Fig 11 on following page 5 Using the ohmmeter touch the probes to RTD lead TS2 WHT A and lead TS2 RED B See Fig 9 Note the resistance Touch the probes to lead TS2 RED B and lead TS2 RED C to check for con...

Страница 21: ...CTION 4 2 9 1 De energize the heating system Allow fluid to cool 2 Close isolation valves Drain the fluid from the heating tank Locate the RTD that requires replacement See Fig 10 3 Unscrew RTD enclosure cover and disconnect RTD leads from wire connectors See Fig 11 4 Unscrew RTD enclosure from RTD For OCLA RTD enclosure removal both enclosures may need to be removed for access 5 Unscrew RTD from ...

Страница 22: ...placement elements may be a different phase configuration 6 Disconnect the ground green yellow and power electrical wires from the posts inside the cap 7 Unscrew cable gland from conduit connector entrance C Remove element conduit H and wires from the heating element See Fig 12 8 Loosen V clamp screw to remove V clamp D Detach the heating element from the tank as shown 9 Replace the heating elemen...

Страница 23: ...s must be taken to ensure that the heating system is operational for start up Steps must be taken to ensure that water ingress is mitigated at all locations All plugs and caps must remain tight and a suitable cover must be provided for the system The cover must shield the system from direct rain and protect from any directed spray that may occur For any storage longer than three months desiccant b...

Страница 24: ... tripped Check and reset switch If problem occurs again check motor Restart system RTD failure Check TCR and RTD See SECTION 4 2 9 RTD cable failure Check TCR and RTD See SECTION 4 2 9 Fluid temperature too low Motor failure Check motor Replace if necessary Heater has been turned off and fluid is cold Allow time for the heating system to heat fluid Heating element failed Check elements for continu...

Отзывы: