18
KMS-750MLH
Fig. 8
Water Supply Inlet
1/" FPT
Icemak
er
Shut-Off Valve
Drain Valve
Drain Outlet
3/4" FPT
Condensate Drain
5/8" OD Pipe
Bin Drain Outlet
3/4" FPT
Stor
age Bin
Separate piping to approved drain.
Leave a two-inch (5 cm) vertical air gap
between the end of each pipe and the
drain.
Two Inch
(5 cm) Air Gap
Floor
Drain
• Drain outlet for icemaker dump is 3/4" FPT. The drain for condensation is a 5/8" OD
pipe. The icemaker drain and the condensate drain piping connections must be made
separately from the bin drain.
• A vented tee connection is required for proper flow.
• The drains must have 1/4" fall per foot on horizontal runs to get a good flow.
• The drains should not be piped directly to the sewer system. An air gap of a minimum of
vertical inches should be between the end of the drain pipes and the floor drain. See
Fig. 8.
• The icemaker should be installed in accordance with applicable national, state and local
regulations.
• A plumbing permit and services of a licensed plumber may be required in some areas.