g) Dual Temp Unit (S3 dip switch 6)
Dual Temp units require S3 dip switch 6 be placed in the "ON" position for proper
operation.
CAUTION! Do not adjust S3 dip switch 6 out of the factory default
position on this model. This dip switch must be left in the factory default position
or this unit will not operate correctly.
Factory set, no adjustment required.
S3 Dip Switch Setting
Dual Temp Selector Switch
No. 6
OFF
All Models Except Dual Temp
ON
Dual Temp Models
h) Freezer Evaporator Fan Operation (except RFH1) (S3 dip switch 7)
Active when S3 dip switch 1 and S3 dip switch 8 are in the "OFF" position (freezer
application). When S3 dip switch 7 is in the "ON" positon, evaporator fan operates
continuously (except during defrost) and the temperature at which the evaporator fan
resumes after defrost changes from 0°F (-17.7°C) to 70°F (21°C). When set to the
"OFF" position, the evaporator fan cycles on and off with the compressor. After defrost,
evaporator fan resumes when evaporator temperature reaches 0°F (-17.7°C).
Factory set, no adjustment required.
Note: S3 dip switch 7 is ignored when S3 dip switch 1 or S3 dip switch 8 is in the "ON"
position.
S3 Dip Switch Setting
Freezer Evaporator Fan Operation
No. 7
OFF
Evap. Fan Cycles On and Off with the Compressor
After Defrost, Evap. Fan Restarts when Defrost Thermistor Reaches 0°F (-17.7°C)
ON
Continuous Evap. Fan (except during defrost)
After Defrost, Evap. Fan Restarts when Defrost Thermistor Reaches 70°F (21°C)
i) RFH1 Condensate Pan Heater Operation (S3 dip switch 8)
Active when S3 dip switch 1 is in the "OFF" position (freezer application) and S3 dip
switch 6 is in the "ON" position (Dual Temp application). When S3 dip switch 8 is in the
"OFF" position, the condensate pan heater is not active and the evaporator fan cycles
according to S3 dip switch 7 setting. When S3 dip switch 8 is in the "ON" position, the
control board energizes the condensate pan heater through the control board X5 relay
(on when compressor is off) and the evaporator fan runs continuously (except in defrost).
CAUTION! Do not adjust S3 dip switch 8 out of the factory default position on this
model. This dip switch must be left in the factory default position or this unit will
not operate correctly.
Factory set, no adjustment required.
Note: S3 dip switch 8 is ignored when S3 dip switch 1 is in the "ON" position or S3 dip
switch 6 is in the "OFF" position.
S3 Dip Switch Setting
RFH1 Condensate Pan Heater Operation
No. 8
OFF
X5 Relay Controls Condenser Fan Motor
Evap. Fan Defaults to S3 Dip Switch 7 Setting
ON
X5 Relay Controls Condensate Pan Heater
Continuous Evap. Fan (except during defrost)
After Defrost, Evap. Fan Restarts when Defrost Thermistor Reaches 0°F (-17.7°C)