27
1) Defrost Control
A thermistor (semiconductor) is used for a defrost control sensor. The resistance varies
depending on the suction line temperatures. The thermistor detects the temperature of
the evaporator outlet to start the defrost timer. No adjustment is required. If necessary,
check for resistance between thermistor leads, and visually check the thermistor
mounting, located on the suction line next to the evaporator outlet.
Temperature (°F) Resistance (k
Ω
)
0
14.401
10
10.613
32
6.000
50
3.871
70
2.474
90
1.633
Check a thermistor for resistance by using the following procedures.
(i) Disconnect the connector K3 on the board.
(ii) Remove the thermistor. See “V. 11. Removal and Replacement of Thermistor.”
(iii) Immerse the thermistor sensor portion in a glass containing ice and water for 2 or 3
minutes.
(iv) Check for a resistance between thermistor leads.
Normal reading is within 3.5 to 7 k
Ω
. Replace the thermistor if it exceeds the normal
reading.
2) Defrost Timer
No adjustment is required under normal use, as the defrost timer is adjusted to the suit-
able position. However, if necessary when all the ice formed on the evaporator does not
fall into the bin in the harvest cycle, adjust the defrost timer to longer setting by adjusting
the dip switch (no. 1 & 2) on the controller board.
SETTING
TIME
Dip Switch
Dip Switch
No. 1
No. 2
OFF
OFF
60 seconds
ON
OFF
90 seconds
OFF
ON
120 seconds
ON
ON
180 seconds
Содержание KMD-700MAH
Страница 11: ...11 7 Condensing Unit URC 12F...
Страница 34: ...34 b KMD 700MWH and KMD 900MWH Note KMD 900M_H models have two expansion valves...
Страница 35: ...35 c KMD 700MRH and KMD 900MRH Note KMD 900M_H models have two expansion valves...
Страница 38: ...38 b1 KMD 700MRH auxiliary code R 0 and earlier Note Pressure Switch Cut out 412 PSIG Cut in 327 21 PSIG 21 0...
Страница 39: ...39 b2 KMD 700MRH auxiliary code R 1 and later Note Pressure Switch Cut out 412 PSIG Cut in 327 21 PSIG 21 0...
Страница 42: ...42 Note Pressure Switch Cut out 412 PSIG Cut in 327 21 PSIG 21 0 d1 KMD 900MRH auxiliary code R 0 and earlier...
Страница 43: ...43 d2 KMD 900MRH auxiliary code R 1 and later Note Pressure Switch Cut out 412 PSIG Cut in 327 21 PSIG 21 0...
Страница 75: ...75 Fig 5 Top View Drain Plug Water Shield Overflow Cap Overflow Pipe Cube Guide A Cube Guide B...