![Hoshizaki KM-251BAH Скачать руководство пользователя страница 23](http://html1.mh-extra.com/html/hoshizaki/km-251bah/km-251bah_service-manual_2165432023.webp)
23
disconnect the float switch by unplugging the harness from the K5 connector. The unit
should switch out of the freeze cycle.
Note: At this point, after the initial freeze cycle and every 10th cycle thereafter, LEDs
1, 3, and 2 come on, the compressor continues to run, the hot gas valve opens
and the fan motor de-energizes. The pump motor stops for 2 seconds. The pump
motor restarts and runs for 10 seconds.
Diagnosis:
If the evaporator is not cold, check to see if the hot gas valve is still open
or if the expansion valve is not opening properly, if the harvest water valve or harvest
valves relay is stuck open (the freeze water valve will cycle on and off during freeze), if
there are improper unit pressures, or an inoperative compressor. If the unit remains in
freeze with the float switch removed, replace the board.
Note: Normal freeze cycle will last 20 to 40 minutes depending on model and
conditions. Cycle times and pressures should follow performance data provided
in this manual.
6)
Normal Harvest Cycle
– same as the initial harvest cycle – Return to step 4.
Note: Unit continues to cycle until bin control is satisfied or power is switched OFF. The
unit always restarts at the 1 minute fill cycle.
B. Diagnostic Charts
1. No Ice Production
Problem
Possible Cause
Remedy
[1] The icemaker will not
start.
a) Power Supply
1. Off (breaker tripped or
fuse blown).
1. Reset breaker or replace
fuse.
2. Loose connection.
2. Tighten.
3. Bad contacts.
3. Check for continuity and
replace.
4. Voltage too high or too
low.
4. Check and get
recommended voltage.
b) Control Switch
1. OFF position.
1. Move to ICE position.
2. Bad contacts.
2. Check for continuity and
replace.
c) Fuse (internal)
1. Blown.
1. Check for short circuit and
replace.
d) Bin Control
1. Tripped with bin filled
with ice.
1. Remove ice.
2. Improperly activated.
2. Check for proper position
and movement.
e) High Pressure Control 1. Bad contacts.
1. Check for continuity and
replace.
2. Dirty air filter or
condenser.
2. Clean.
3. Ambient or condenser
water temperature too
warm.
3. Reduce temperature.
4. Refrigerant
overcharged.
4. Recharge.