4.4 Primary Power Port
Table 4.1
–
Primary Power Port Pins
PIN
Signal
Description
Frame Ground
-
0V
Input power supply ground
+
+24V
Input power supply positive voltage
Figure 4.1
–
Power Connector (Primary Power Port)
Figure 4.2
–
Primary Power Port
--
+
+
-
10-30VDC
supply
-
+
+
-
DC INPUT / FRAME
Solid/Standard Wire: 12-24 awg (2.5-0.2mm).
Strip Length:
0.28”
(7mm).
Torque Rating: 4.5
–
7 in-lbs (0.50
–
0.78 N-m).
DC- is internally connected to I/O, but is isolated from
CAN-V.
A Class 2 power supply must be used.