MAN0878-09-EN_XLE_XLT_UserManual
A u g u s t 2 3 , 2 0 1 8
P a g e 17 | 158
Once the panel design has been completed using the criteria and suggestions in the following
sections, use the following steps to panel mount the XLE/XLT.
1. Remove all connectors from the XLE/XLT unit.
2. Press the DIN rail clip up to make passing the unit through the cutout easier.
3. Make sure the gasket is installed on the XLE/XLT and is free from dust and debris. Check that
the corners of the gasket are secure.
4. Pass the unit through the panel.
5. Insert the each of the four (4) mounting clips into the slots in the XLE/XLT case. One clip
should be installed on each corner. Lightly tignten each screw so the clip is held in place.
6. Tighten the screws on the clips such that the gasket is compressed against the panel.
Recommended torque is 7-10 in-lbs [0.8-1.13 Nm]).
3.2.2 Mounting Procedures (Installed on DIN Rail)
Figure 3.2
–
DIN Rail Mounting of the XLE/XLT
The XLE/XLT is designed to clip onto standard 35mm DIN rail. If your installation requires
liquid or dust protection, make sure the XLE/XLT is placed in an appropriate sealed panel
when mounting on DIN rail. Use the following steps to mount the XLE/XLT on DIN rail.
1.
Move the DIN rail clip to the lower position.
2.
Clip the “Top Clips” on the top of the DIN r
ail.
3.
Press the unit into place and press the DIN rail clip up. A small flat-head screwdriver
can be used in the slot of the DIN rail clip if clearance is an issue.
NOTE: The DIN rail connection does not provide an earth ground. Refer to
Page 20
for proper
grounding information.
DIN
Rail Clip
Top
Clip
NOTE: Mount the XLE/XLT with
the DIN Rail in the horizontal
position to avoid slippage.