5.3.3.
Switching mode (charge/discharge mode)
Characteristics of this operating mode are:
When charging, the battery is disconnected from the consumer.
The battery can be switched to the consumer as required.
The charging voltage of the battery is max. 1.50...1.60 V/cell (boost charge) or
1.40...1.45 V/cell (float charge), see also Section 5.3.1.
The battery also can be charged with constant current I
5
. A secure shutdown criterion is
required for this. Voltages up to 1.9 V / cell can occur.
The charging process must be monitored.
Secured shutdown criterion required (up to 1.9V/cell)
Direct
current
source
Load
Battery
Charger