Hoppecke 5 OPzV 250 Скачать руководство пользователя страница 17

32

33

Installation, commissioning and operating instructions for valve-regulated stationary lead-acid batteries
7140203153 V1.4 (09.2018)

Installation, commissioning and operating instructions for valve-regulated stationary lead-acid batteries

7140203153 V1.4 (09.2018)

5.10 Connecting the batteries

The batteries are in their final position and can now be connected.

5.10.1 Connection terminals

The battery terminals of the types 

sun

| power 

VR M

  12 V 58 – 12 V 90 have been greased at 

the factory using Aeronix® battery terminal grease. Inspect each terminal for visible damage or 
oxidation. If necessary you should clean the terminal by using a brush (with hard plastic bristles). 
Re-grease by using the above mentioned terminal grease.
Other sealed lead acid battery types don’t need to be greased because the terminals are rubber 
molded.

5.10.2 Type of connection cable

The battery system that you received is designed to produce a specified amount of power (kW) or current (A) at 
a particular voltage for a certain period of time (standby time).
You should be familiar with these parameters (U, kW, A). If this is not the case, please contact your local 
HOPPECKE representative.

The battery system was designed so that the electrical energy is available at the battery terminals.
Limit voltage drop between the battery terminals and electrical loads to an absolute minimum. If 
the voltage drop is too large, the backup time of the battery system may be reduced.
Observe the following information:
1.  Keep the cable length between the batteries and the charging rectifier/USV as short as pos-

sible.

2.  The cable cross-section should be calculated so that voltage drop is negligible even at a high 

current flow. Use the cross-section of the cable provided to calculate the voltage drop at the 
nominal current. If in doubt, use cable with a cross-section that is one size larger.

  Danger!

The connection cable must be short-circuit proof or double-wall insulated. That means:
–  The insulation strength of the cable is higher than the max. system voltage or
– there is a distance of at least 100 mm between wiring and electrically conductive parts or
– connectors must be furnished with additional insulation.
–  Avoid mechanical stress on the cell/battery terminals. Protect cables with large cross-sections 

using cable ties and cable clamps.

The connection cables between the main connection terminals and the charging rectifier or UPS 
should be flexible conductors.

5.10.3 Clamping batteries using battery connectors

There are screwed row, step and tier connectors 

(see Fig. 5–15)

.

Row connectors are used to connect the individual cells/monobloc batteries, step connectors 
are used to connect the individual steps to one another (for use with step racks) and the tier 
connectors are used to connect the tiers (for use with tier racks).

Fig. 5–15: Using row connectors and step connectors

 Attention!

Row, step, tier and end connectors are designed as screwed connectors. After loosening a con-
nection, the assembly screws must always be replaced.

5.10.4 Installing the screwed connectors

1.   The batteries are connected using the insulated row connectors (Fig. 

5–16). When establishing the serial connection, the batteries are arran-
ged so that the negative terminal of one battery is connected to the 
positive terminal of the next battery until the entire system has reached 
the necessary voltage.

Make sure that you do not cause mechanical damage to 
the terminals.

Attention!

2.   Attach the connectors as shown in

 Fig. 5–15.

 First attach the screws 

by hand only so that you can make final adjustments to the cells and 
connectors.

3.  Tighten the screws using a torque wrench. The recommended torque is 

20 Nm ±1 Nm.

It is very important to tighten screws thoroughly as a loose 
connection can become very hot and result in ignition or 
explosion.
Screws are approved for single use only!

 Attention!

4.   If necessary, fit the connectors and end terminals (connection plates) 

with insulating covers.

5.10.5 Clamping connection plates onto the batteries

There are a total of 11 different types of connection plates 

(see Fig. 5–15)

. Connection plates are 

always used when wires must be connected to cells with multiple battery terminals.

Attention!

We strongly recommend that you use original HOPPECKE connection plates when connecting 
wires to cells with multiple battery terminal pairs. Using other solutions may lead to overhea-
ting, risk of fire and increased electrical contact resistance!

Fig. 5–16: Screwed connector 
installation

Содержание 5 OPzV 250

Страница 1: ...for valve regulated stationary lead acid batteries Installation commissioning and operating instructions Similar to the illustration...

Страница 2: ...development For this reason there may be discrepancies between the product that you have purchased and the product as represented in this documentation Please keep this documentation so that it is im...

Страница 3: ...ely from normal household wastes General notice or tip for better understanding and optimum use of the battery or batteries Pb 0 Safety notices 0 1 General Information Danger Incorrect use of the prod...

Страница 4: ...ive counterparts of old and new names In the rest of this document old names will be listed in brackets Pb Following symbols and pictograms are pictured on each battery cell or on each battery block R...

Страница 5: ...e for Maintenance Testing and Replacement of Valve Regulated Lead Acid VRLA Batteries for Stationary Applications IEEE Standard 1189 2007 Guide for Selection of Valve Regulated Lead Acid VRLA Batterie...

Страница 6: ...ls blocks into the racks 30 5 10 Connecting the batteries 32 5 10 1 Connection terminals 32 5 10 2 Type of connection cable 32 5 10 3 Clamping batteries using battery connectors 32 5 10 4 Installing t...

Страница 7: ...type 250 Nominal capacity C10 capacity during discharge with ten hours current I10 over a discharge time of 10 h t10 267 actual capacity C10 capacity of discharge with 10 h current 5 OPzV 250 2V 250A...

Страница 8: ...ly However they contain diluted sulfuric acid H2 SO4 that is bonded in gel or glass mat The bonded sulfuric acid is extremely corrosive and can cause serious injury Further information to sulfuric aci...

Страница 9: ...ic shock If a second accidental ground connection is made there is a risk of short circuit fire and explo sion If you have questions about these instructions or any other questions regarding safety wh...

Страница 10: ...r is still present to make sure that your shipment is complete compare with the delivery note In particular check the number of battery pallets and the number of boxes with accessories Then inspect th...

Страница 11: ...ention If the cells batteries are to be stored for a long period of time store them fully charged in a dry frost free location Avoid direct sunlight To prevent damage to the batteries an equalizing ch...

Страница 12: ...cell width installation depth at least 500 mm see also IEC 62485 2 USA 36 or 915 mm HOPPECKE recommendation If possible at the installation location 1 m Otherwise in accordance with local regulations...

Страница 13: ...always filled before delivery Sealed stationary lead acid battery cells must not be refilled with water during the entire battery service life Overpressure valves are used as sealing plugs These plugs...

Страница 14: ...d ventilation for hydrogen generated by batteries Chap 10 Required ventilation for hydrogen generated by bat teries 5 3 Conducting an open circuit voltage measurement Before installing the batteries c...

Страница 15: ...c tions mask bad cells and blocks and could cause individual battery strings to overload 2 Only batteries of the same type and same state of charge should be connected same battery type plate size and...

Страница 16: ...e after another into the racks so that they are angled and level with the correct polarity Remove all transportation and hoisting equipment For large batteries it is required that you begin installati...

Страница 17: ...rs must be furnished with additional insulation Avoid mechanical stress on the cell battery terminals Protect cables with large cross sections using cable ties and cable clamps The connection cables b...

Страница 18: ...brations which could loosen the connection under certain cir cumstances The cables must be supported so that no mechanical load can be transferred to the connection terminals cable trays cable ducts c...

Страница 19: ...n be omitted 6 1 Discharging Attention Never allow the final discharge voltage of the battery to drop below the voltage corresponding to the discharge current Unless the manufacturer has specified oth...

Страница 20: ...ber of cells in series occurs after charging DC power supply Electrical Load Battery 6 2 2 Floating operation The following is characteristic for this operating mode Consumers direct current source an...

Страница 21: ...on of the equalizing charge Perform the equalizing charge as follows 1 Charging with IU characteristic up to max voltage U 2 4 V cell up to 48 hours The charge current must not be higher than 20 A per...

Страница 22: ...power VR L OPzV solar power OPzV bloc solar power and sun power VR M solar bloc batteries This chapter contains instructions for charging of HOPPECKE sun power VR L OPzV solar power OPzV bloc solar p...

Страница 23: ...charge of 80 Fig 7 9 Endurance in cycles of sun power VR L OPzV solar power as a function of ambient temperature Cycle Number n Depth of Discharge DoD Cycles n Ambient Temperature in C 7 3 Temperature...

Страница 24: ...depicts dependency of the endurance in cycles on depth of discharge and temperature Fig 7 10 Endurance in cycles of sun power VR L OPzV solar power depending on DoD and temperature 7 4 3 Electrolyte f...

Страница 25: ...mum voltage is reached 11 Reconnect the battery system as originally connected and perform a boost charge see Chap 5 13 9 2 Performing the capacity test extended version Preparation The best and quick...

Страница 26: ...ecting the correct discharge current or the correct discharge power Carry out the battery discharge in accordance with the regulations on performing capacity tests EN 60896 21 The discharge current an...

Страница 27: ...ells The battery is on float charge at 2 25 V per cell CN Nominal capacity of the battery 200 Ah n Number of cells 2 x 30 cells fg Gas emissions factor 0 2 fs Safety factor 5 Ifloat 1 mA Ah Cell numer...

Страница 28: ...w of 0 6 m3 h What factors must be considered when installing a natural ventilation system If possible the ventilation openings should be positioned on opposite walls If they must both be on the same...

Страница 29: ...fire extinguishers are not suitable amongst others because of only minor efficiency possible risks or collateral damages Special protective equipment For larger stationary battery installations or lar...

Страница 30: ...67 no transport as dangerous goods non spillable batteries are not subject to other requirements of IATA DGR if they meet the requirements of Special Provision A 67 Provided that poles are secured ag...

Страница 31: ...correct or up to date Packing Instruction P 801 a transport as dangerous packing in accu Special Provision VV 14 transport as dangerous ADR Tunnel restriction code Note these references can be applie...

Страница 32: ...on dispose with due regard to the official local regu lations 7 Handling and storage Store frost free under roof Seek agreement with local water authorities in case of larger quan tities Observe VAWS...

Страница 33: ...l details in this brochure are based on state of the art technology Our products are subject to constant development We therefore reserve the right to make changes HOPPECKE Batterien GmbH Co KG P O Bo...

Отзывы: